Fig. 40—Example of Field Drain Attachment
CONDENSATE TRAP
WIRE TIE(S)
HEAT TAPE
(3 WRAPS MINIMUM)
Fig. 41—Condensate Trap Heat Tape
Blower reverts to continuous operation after heating cycle is
completed.
If a call for cooling (R-Y) occurs while thermostat is in continuous
blower mode, blower changes from continuous blower speed
(heating speed) to cooling speed.
When thermostat cooling call is satisfied, R-Y opens and blower
operates an additional 90 see at cooling speed before reverting
back to continuous operation (heating speed).
D. HEAT PUMP MODE
When installed with a heat pump, furnace control automatically
changes blower on delay timing sequence to avoid no blower
operation time during demand defrost cycles. When R-W and R-Y
or R-W, R-Y, and R-G thermostat inputs are received at the same
time at furnace control center, control starts blower in heating
speed. Then a gas heat mode begins. Blower remains operating at
heating speed for 15 sec or until end of prepurge period, then
blower shuts off until end of ignitor warm up and trial for ignition
periods (a total of 24 sec). Blower restarts at heating speed.
When R-W thermostat call disappears, control completes inducer
post-purge period of 15 sec (5 sec if jumper has been cut for 140
size unit in downflow orientation) and changes to cooling speed
after a 2-sec delay.
If R-W, R-Y, and R-G thermostat signals should disappear
simultaneously, blower remains on for selected heating blower off
delay period (90, 135, 180, or 225 sec), and the inducer goes
through 15 sec post-purge period (5 sec if jumper has been cut for
140 size unit in downflow orientation). If R-W and R-Y thermostat
signals should disappear, leaving R-G thermostat signal, blower
remains on in heating speed and inducer remains on for 15 sec (5
sec if jumper has been cut for 140 size unit in downflow
orientation) to complete post-purge period.
Control initiates a 90-sec blower only on period before starting
another heat pump cycle if there is a power interruption. Anytime
control senses false flame, control locks out of heating mode. This
reaction occurs because control ignores W input due to false flame
signal and, as a result, sees only Y input and goes into cooling
mode blower off delay. All other control functions remain in
standard format.
NOTE: EAC-1 terminal is energized whenever blower operates.
HUM terminal is only energized when gas valve is energized.
A94054
E. COMPONENT TEST
COMPONENT TEST SEQUENCE
NOTE: All components are functionally operated except the gas
valve.
When component test is initiated, the following sequence of events
occurs:
1. LED flashes a status code 4 times.
2. Inducer motor starts and continues to run for remainder of
component test.
3. Hot surface ignitor is energized for 15 sec, then de-
energized.
4. Main blower operates at cooling speed for 10 sec, then turns
off.
5. Main blower operates at heating speed for 10 sec, then turns
off.
6. Inducer motor stops.
INITIATING COMPONENT TEST BY REMOVING MAIN
LIMIT SWITCH WIRE
NOTE: NO thermostat signal may be present at control center
and all blower time delay off periods must be completed.
A93036
1. Leave 115-v power to furnace turned on.
2. Remove main furnace door.
3. Look into blower access panel sight glass for current LED
status.
NOTE: Leave blower access panel installed to maintain power to
control center to view current LED status.
4. BRIEFLY remove either wire from the main limit switch
until the LED goes out, then reconnect it.
CAUTION: Make sure limit switch wire does not con-
tact any metallic component such as the gas valve. If wire
is shorted, 3-amp fuse on control center will blow.
NOTE: If wire to main limit is disconnected longer than 4 sec, the
control senses limit circuit is open. Main blower will start and
status retrieval request will be ignored.