Bryant 350MAV Installation, Start-Up, And Operating Instructions Manual page 22

Series e &f deluxe 4–way multipoise fixed-capacity direct-vent condensing gas furnace
Table of Contents

Advertisement

115-VAC (L1)
POWER SUPPLY
IGNITOR CONNECTOR
FURNACE
NOT IN
HORIZONTAL
SECTION
Fig. 26—Combustion-Air and Vent Pipe Diameter
Transition Location and Elbow Configuration
CAUTION: Combustion air must not be taken from
inside structure because inside air is frequently contami-
nated by halogens, which include fluorides, chlorides,
bromides, and iodides. These elements are found in
aerosols, detergents, bleaches, cleaning solvents, salts, air
fresheners, adhesives, paint, and other household prod-
ucts. Locate combustion-air inlet as far as possible from
swimming pool and swimming pool pump house.
Excessive exposure to contaminated combustion air will
result in safety and performance related problems.
BLOWER OFF DELAY
ADJUSTMENT SWITCH
TEST/TWIN
SEC-1
3-AMP FUSE
COOL
HEAT
HOT SURFACE
INDUCER MOTOR
CONNECTOR
Fig. 25—Control Center
PIPE DIAMETER
TRANSITION IN
VERTICAL SECTION
A93034
24-V THERMOSTAT
G
TERMINALS
R
Y
W
HUMIDIFIER TERMINAL
Com
(24-VAC 0.5 AMP MAX)
24V
HUM
LED OPERATION &
DIAGNOSTIC LIGHT
HARNESS CONNECTOR
24-V TRANSFORMER SEC-2
SPARE-1
BLOWER SPEED
SELECTION TERMINALS
SPARE-2
EAC-1 (BLACK)
EAC-ELECTRONIC AIR CLEANER
TERMINALS (115-VAC 1 AMP MAX)
EAC-2 (WHITE)
115-VAC (L2) NEUTRAL
CONNECTION
TABLE 5—COMBUSTION-AIR AND VENT PIPE TERMI-
Above grade level or above
anticipated snow depth
From plumbing vent stack
From any mechanical fresh air intake
For furnaces with an input capacity of
100,000 Btuh or less—from any non-
mechanical air supply (windows or doors
which can be opened) or combustion-air
For furnaces with an input capacity greater
than 100,000 Btuh or less—from any non-
mechanical air supply (windows or doors
which can be opened) or combustion-air
From service regulator vent, electric and
gas meters and relief equipment
Above grade when adjacent to public
* Horizontal distance.
† 18 in. above roof surface in Canada.
‡ 36 in. to electric meter in Canada only.
NOTES:
1. If installing 2 adjacent 350MAV Furnaces, refer to Multiventing and Vent
Terminations section for proper vent configurations.
2. When locating combustion-air and vent terminations, consideration must be
given to prevailing winds, location, and other conditions which may cause
recirculation of the appliance's own flue products or the flue products of
adjacent vents. Recirculation can cause poor combustion, inlet condensate
problems, and accelerated corrosion of heat exchangers.
3. Vent termination can not terminate less than 2 ft horizontal and 7 ft above
public walkway or where condensate vapor or droplets may be a hazard.
—22—
NATION CLEARANCES
LOCATION
Dryer vent
opening
opening
walkway
A00292
CLEARANCE (FT)
U.S.A.
Canada
1
1†
3
3
3
3
1
6
1
1
1
3
4*
6‡
Note 3
Note 3