Unconfined Space; Confined Space - Carrier 58UHV Installation, Start-Up, And Operating Instructions Manual

Upflow/horizontal variable-speed, 2-stage induced-combustion gas furnaces sizes 060-120, series 110 and 120
Table of Contents

Advertisement

SUPPLY
AIR
INTERIOR
HEATED
SPACE
RETURN AIR
* Minimum opening size is 100 sq in. with
minimum dimensions of 3 in.
Minimum of 3 in. when type-B1 vent is used.
Fig. 3—Confined Space: Air for Combustion and
Ventilation from an Indoor Unconfined Space
The operation of exhaust fans, kitchen ventilation fans,
clothes dryers, or fireplaces could create a NEGATIVE AIR
PRESSURE CONDITION at the furnace. Make-up air MUST
BE PROVIDED for these devices, in addition to that required
by the furnace.
Combustion and ventilation air requirements are determined by
whether the furnace is located in a CONFINED or UNCONFINED
space.

UNCONFINED SPACE

An unconfined space has volume of at least 50 cu ft for each 1000
Btuh of total input for all appliances (such as furnaces, clothes
dryers, water heaters, etc.) in the space.
For Example:
58UHV AND 58UXV FURNACES
HIGH-STAGE INPUT BTUH
60,000
80,000
100,000
117,000
If the unconfined space is of unusually tight construction, air for
combustion and ventilation MUST come from either the outdoors
or spaces freely communicating with the outdoors. Combustion
and ventilation openings must be sized the same as for a confined
space as defined below. Return air must not be taken from the
room unless an equal or greater amount of air is supplied to the
room.
VENT THROUGH ROOF
12" MAX
1 SQ IN.
PER 1000
BTUH * IN DOOR
OR WALL
UNCONFINED
SPACE
6" MIN
(FRONT)
1 SQ IN.
PER 1000
BTUH * IN DOOR
OR WALL
12" MAX
A89012
MINIMUM SQ FT WITH
7-1/2 FT CEILING
400
534
667
780
OUTDOORS
12" MAX
1 SQ IN.
PER 2000
BTUH*
DUCTS
TO
OUTDOORS
1 SQ IN.
PER 2000
BTUH*
12" MAX
RETURN AIR
*Minimum dimensions of 3 in.
NOTE:
Use any of the following
combinations of openings:
A & B
Fig. 4—Confined Space: Air for Combustion and
Ventilation from Outdoors

CONFINED SPACE

A confined space is defined as a space whose volume is less than
50 cu ft per 1000 Btuh of total input ratings of all appliances
installed in that space. A confined space MUST have provisions
for supplying air for combustion, ventilation, and dilution of flue
gases using 1 of the following methods. (See Fig. 3 or 4, and Table
2.)
NOTE: In determining free area of an opening, the blocking
effect of louvers, grilles, and screens must be considered. If free
area of louver or grille design is unknown, assume that wood
louvers have a 20 percent free area and metal louvers or grilles
have a 60 percent free area. Screens, when used, must not be
smaller than 1/4-in. mesh. Louvers and grilles must be constructed
so they cannot be closed.
The size of the openings depends upon whether air comes from
outside of the structure or an unconfined space inside the structure.
1. All air from inside the structure requires 2 openings (for
structures not usually tight):
a. Each opening MUST have at least 1 sq in. of free area per
1000 Btuh of total input for all equipment within the
confined space, but not less than 100 sq in. per opening.
(See Fig. 3 and Table 2.) The minimum dimension of air
openings shall not be less than 3 in.
b. If building is constructed unusually tight, a permanent
opening directly communicating with the outdoors shall be
provided. (See item 2 below.)
c. If furnace is installed to obtain a return-air directly from
hallway or space adjacent to furnace, all air for combustion
must come from outdoors.
5
1 SQ IN.
PER 4000
DUCTS
BTUH*
TO
D
VENT
A
THROUGH
F
SUPPLY
ROOF
AIR
E
G
B
C
12" MAX
DUCT
1 SQ IN.
TO
PER 4000
OUTDOORS
BTUH*
C & D
D & E
F & G
12"
MAX
1 SQ IN.
PER
4000
BTUH*
1 SQ IN.
PER
4000
BTUH*
12"
MAX
A89013