Remove the small black cap (covering 1-1/16" diameter
hole) from back of enclosure. Remove threaded lock
nut from conduit coupling (with 90° elbow) and wires.
Feed wires into 1-1/16" diameter hole. Place threaded
lock nut over wires and onto conduit coupling. Tighten
securely with screwdriver and hammer to ensure lock nut
is tight. Connect power leads (red & black) to the circuit
breaker lugs. Connect the neutral wire (white) to terminal
connection (NEUTRAL). Connect ground wire (green) to
grounding bolt with star washer below all ground wire
lugs. Tighten securely ensuring the star washer makes
good contact with metal base plate. Connect sensing
wires to terminal strip as follows: Blue - N1, Yellow - N2,
Brown - 23 and Orange - 194.
FUEL HOOKUP AND CHECK FOR LEAKS
21a. Make the connection between the rigid fuel piping and the
generator using the supplied threaded flexible fuel line.
Use a pipe sealant suitable for gaseous fuel connections.
Check connections for leaks by opening manual fuel shut-
off valve and swab, or spray, connections with soapy water.
If a leak exists, the area will bubble with the presence of the
soapy water.
Grounding
Lug
19
One (1) Foot Flexible
21
Fuel Line
Residential Transfer Switch Installation Guide
21b. If a leak is located, shut off fuel and disconnect flexible
piping. Dry the threaded ends and reapply an adequate
amount of pipe sealant. Reconnect flexible fuel line,
open fuel supply and recheck for leaks. If leak still
exists, repeat step 21b.
22. Follow all generator installation and setup instructions
in the Installation and Owner's Manual provided with the
generator. During testing performed in Section 2 of the
generator Installation and Owner's Manual, utility power
supply to the Automatic Transfer Switch/Load Center
can be controlled using the 40 or 70 amp feeder circuit
breaker located in the main distribution panel.