OPERATING PROCEDURE
4. Removing the fan
Note : Perform the following with the indoor unit lowered down
to the floor.
! Remove the drain pan.
@ Disconnect the connector for the fan motor.
# Take out the fan after removing the 7 set screws of the fan
plate.
$ Unscrew four set screws of the bell mouth and remove the
bell mouth.
% Loosen the set screw of the fan to pull out the sirocco fan.
^ Unscrew the four set screws of the motor fitting, and
remove the fan motor.
Photo 7
Bell mouth
Set screw
(See Photo 1)
(See Photo 3)
(See Photo 5 or 6.)
(See Photo 7.)
(See Photo 7.)
(See Photo 8.)
Fan casing
Sirocco fan
Fan plate
Fixture set screw
40
PHOTOS
Photo 5
Set screw
Photo 6
Fan casing
Photo 8
Fixture set screw
Fittings
Fan plate
Fan motor
Fan plate
Set screw
Fan motor