NOTES : Wiring between generator and electrical appliances
1. Allowable current of cable Use a cable with an allowable current that is higher than the rated
input current of the load (electrical appliance). If the input current is higher than the allowable
current of the cable used, the cable will become excessively heated and deteriorate the insula-
tion, possibly burning it out.
Table 7-2 shows cables and their allowable currents for your reference.
2. Cable length
If a long cable is used, a voltage drop occurs due to the increased resistance in the conduc-
tors decreasing the input voltage to the load (electrical product). As a result, the load can be
damaged.
Table 7-2 shows voltage drops per 100 meters of cable.
Nominal
A.W.G.
cross
Gauge
section
No.
mm
2
No.
0.75
18
1.27
16
2.0
14
3.5
12 to 10
5.5
10 to 8
Voltage drop indicates as V=
R
means resistance (
means electric current through the wire (A).
I
means the length of the wire (m).
The length of wire indicates round length, it means twice the length from generator to
electrical tools.
Allowable
No.of strands
Resistance
current
/ strands dia.
A
No./mm
/100m
7
30/0.18
2.477
12
50/0.16
1.486
17
37/0.26
0.952
23
45/0.32
0.517
35
70/0.32
0.332
1
R I
100
/ 100 m) on the above table.
Current Amp.
1A
3A
5A
2.5V 8V 12.5V
1.5V 5V 7.5V 12V 15V 18V
1V
3V
5V
1.5V 2.5V 4V
1V
2V 2.5V 3.5V 4V
22
8A 10A 12A 15A
8V 10V 12V 15V
5V 6.5V 7.5V
5V