The installer must supply an external regula-
tor. The external regulator will reduce incom-
ing gas pressure. You must reduce incoming
gas pressure to between 11" and 14" of water.
If you do not reduce incoming gas pressure,
heater regulator damage could occur. Install
external regulator with the vent pointing down
as shown in Figure 13. Pointing the vent down
protects it from freezing rain or sleet.
Ground
Joint Union
Tee Joint
Reducer
Bushing to
Test Gauge
1/8" NPT
Connection*
1/8" NPT
Plug Tap
Tee Joint
Sediment
Pipe Nipple
Trap
Gap
Figure 12 - Gas Connection
* Purchase the optional CSA design-certified equipment
shutoff valve from your dealer.
Gas Regulator
Inlet Connector
14
INSTALLATION
3/8" NPT
Pipe Nipple
3" Minimum
Figure 14 - Gas Regulator Location and
Gas Line Access into Stove Cabinet
www.sureheat.com
Install sediment trap in supply line as shown
in Figure 12. Place sediment trap where it is
within reach for cleaning. Place sediment trap
where trapped matter is not likely to freeze.
A sediment trap traps moisture and contami-
nants. This keeps them from going into heater
controls. If sediment trap is not installed or is
installed wrong, heater may not run properly.
Equipment
Shutoff Valve
Propane/LP
Supply Tank
Natural Gas
From Gas Meter
(5" W.C.** to 9"
W.C. Pressure)
Propane/LP
From External
Regulator
(11" W.C.**
to 14" W.C.
Pressure)
Figure 13 - External Regulator
with Vent Pointing Down
External
Regulator with
Vent Pointing
Down
200176-01A