DX Air Curtain
4
ELECTRICAL WORK
1. Using the specified wires, ensure to connect
the wires, and fix wires securely so that the
external tension to the wires do not affect the
connecting part of the terminals.
Incomplete connection or fixation may cause a fire,
etc.
2. Be sure to connect earth wire (grounding work).
Incomplete grounding cause an electric shock.
Do not connect ground wires to gas pipes, water
pipes, lightning rods or ground wires for telephone
wires.
3. Appliance shall be installed in accordance with
national wiring regulations.
Capacity shortage of power circuit or incomplete
installation may cause an electric shock or a fire.
• This indoor unit has no power cord.
• If incorrect / incomplete wiring is carried out, it will
cause an electrical fire or smoke.
• Install an earth leakage breaker.
If an earth leakage breaker is not installed, an
electric shock may be caused.
• Be sure to use the cord clamps attached to the
product.
• Do not damage or scratch the conductive core and
inner insulator of power and inter-connecting wires
when peeling them.
• Use the power cord and inter-connecting wire of
specified thickness, type and protective devices
required
REQUIREMENT
• For power supply wiring, strictly conform to the
Local Regulation for each country.
• For wiring of power supply of the outdoor units,
follow the Installation manual of each outdoor unit.
• Never connect 220-240V power to the terminal
blocks (
, etc) for control wiring (otherwise the
system will fail).
• Perform the electric wiring so that it does not come
in to contact with the high-temperature part of the
pipe.
The coating may melt in an accident
• After connecting wires to the terminal blocks, be
sure to leave sufficient wire before fixing with the
cord clamp.
• Run the refrigerant piping and control wiring line in
the same line.
WARNING
CAUTION
• Do not turn on the power of the indoor unit until
vacuuming of the refrigerant pipes is completed.
Remote controller wiring
2-core non polarity wire is used for the remote
controller wiring.
How to wire
1. Connect the wires from the terminal block on the
outdoor unit to the same numbered terminal on
the DX Air Curtain terminal block. Use wires to
H07 RH-F or 60245 IEC 66 (1.5mm
2. In the case of unsheathed redundant cords
(conductors) be sure to insulate with electrical
insulation tape.
Fix them so that they do not touch any electrical
or metal parts.
REQUIREMENT
• Be sure to connect the wires matching the
terminal numbers. Incorrect connection causes a
trouble.
• Be sure to pass the wires through the bushing of
the wiring connection port of the DX
6
Installer
2
or more).