Toshiba RAV-CT100-M Installation And Owner's Manual page 13

Dx air curtain
Table of Contents

Advertisement

DX Air Curtain
Remote controller switch monitoring function
This function is available to call the service monitor mode from the remote controller during a test run to acquire
temperatures of sensors of the remote controller, indoor unit and outdoor unit.
1. Push
and
buttons simultaneously for at least 4 seconds to call the service monitor mode.
The service monitor indicator lights up and the header indoor unit number is displayed first. CODE No.
displayed.
2. Pushing TEMP.
table).
3. Pushing
(left side of button), select an indoor unit in the group to be monitored. The sensor temperatures
of indoor units and their outdoor unit in the control group are displayed.
4. Push
button to return to the normal display.
Indoor Unit Data
CODE No.
01
Room temperature (remote controller)
02
Indoor unit intake air temperature (TA)
Indoor unit heat exchanger (coil)
03
Indoor unit heat exchanger (coil)
04
Indoor unit fan cumulative operating
F3
buttons, select the number of sensor, etc. (CODE No.) to be monitored (see the following
Data Name
temperature (TCJ)
temperature (TC)
hours (x1 h)
Outdoor Unit Data
CODE No.
Outdoor unit heat exchanger (coil)
60
61
62
Compressor discharge temperature (TD)
63
Compressor suction temperature (TS)
64
65
6A
Compressor cumulative operating hours
F1
14
Data Name
temperature (TE)
Outside air temperature (TO)
Heat sink temperature (THS)
Operating current (x1/10)
(x100h)
Installer
is also

Advertisement

Table of Contents
loading