Item
Description of operation, numerical data, and other information
2. Outdoor
1. Cooling fan control
fan control
1) Outdoor fan speed (mode) is controlled on the basis of measurements provided by
the Pd pressure sensor.
2) For a specified period after the start of cooling operation, the header outdoor unit
controls outdoor fan speed (mode) on the basis of measurements provided by the
Pd pressure sensor. Follower units, on the other hand, control outdoor fan speed
(mode) on the basis of measurements provided by the TE1 temperature sensor.
Pd
pressure
3.0
2.65
2.45
2.35
2.15
2.00
1.95
* Available control modes are 0 (at rest) to 63.
2. Heating fan control
1) Outdoor fan speed (mode) is controlled on the basis of measurements provided by
the TE1 temperature sensor.
2) If TE1 > 25°C is continuously detected for 8 minutes, the fan may be turned off.
However, this condition is the same as normal thermo OFF, so that fan operation
will be restarted.
3) For a specified period after air conditioner startup and during defrosting, this
control is disabled.
4) When refrigerant is in extremely short supply, this control may cause the air
conditioner to be repeatedly turned on and off.
TE1 temperature
(°C)
3. Control while follower unit at rest
The fan is operated at mode 1 to prevent the accumulation of refrigerant inside the
outdoor heat exchanger.
3. Capacity
1) The compressors of the header and follower units are controlled on the basis of
control
capacity demand issued by indoor controllers.
2) The two or three compressors featured in an outdoor unit operate on a rotational
basis, so that, every time they come to a stop, their order of startup changes.
3) Where two or more follower units are connected, every time the system goes
thermo OFF or all the compressors featured in the follower units come to a stop,
the priority startup order of the follower units changes, as they are also subject to
rotational operation.
[Highest mode]
[Current mode - 1]/50 seconds
Mode being lowered:
Highest mode - 1 → 1
[Current mode - 1]
(Mode lowered as rapidly as
every two seconds)
(down to mode 0)
Zone A: Lowest mode, timer count for forced compressor shutdown
25
Zone B: -2/15 seconds (down to lowest mode)
8
Zone C: -1/15 seconds (down to lowest mode)
6
Zone D: Hold (staying at current mode)
4
Zone E: +1/15 seconds (up to highest mode)
2
Zone F: Highest mode
[Current mode + 1]
(Mode raised as rapidly
as every second)
[Current mode + 1]/50 seconds
[Current mode + 1]/75 seconds
(Mode raised up to 13)
[Hold]
(Mode 1 to highest)
Mode being raised: mode 0 → 1
Interval control
[Mode [0]: 180 seconds
Mode [1]: 30 seconds]
– 75 –
Remarks
• The fan speed
corresponding to the highest
mode varies with the HP
capacity of the outdoor unit.
• The fan speed
corresponding to the highest
mode varies with the HP
capacity of the outdoor unit.