Toshiba MMY-MAP0804HT8JP Service Manual page 144

Air-conditioner (multi type)
Hide thumbs Also See for MMY-MAP0804HT8JP:
Table of Contents

Advertisement

Wireless remote controller
(4-way Cassette type)
Test run (Forced cooling operation)
Requirement:
• Finish the forced cooling operation in a short
time because it applies excessive strength to the
air conditioner.
How to perform forced cooling operation
1. When TEMPORARY button is pushed for 10
seconds or more, "Pi!" sound is heard and the
operation changes to a forced cooling operation.
After approx. 3 minutes, a cooling operation starts
forcedly.
Check cool air starts blowing. If the operation does
not start, check wiring again.
2. To stop a test operation, push TEMPORARY
button once again (Approx. 1 second).
• Check wiring / piping of the indoor and outdoor
units in forced cooling operation.
TEMPORARY
button
Test operation from the outdoor unit
• Refer to "7-7-2. Function to Start/Stop (ON/OFF) Indoor Unit from Outdoor Unit" in "7-7. Service Support
Function."
Note:
The test operation returns to normal operating mode after 60 minutes.
Wireless remote controller
(Ceiling type)
Test run (Forced cooling operation)
Requirement:
• Finish the forced cooling operation in a short
time because it applies excessive strength to the
air conditioner.
How to perform forced cooling operation
1. When TEMPORARY button is pushed for 10
seconds or more, "Pi!" sound is heard and the
operation changes to a forced cooling operation.
After approx. 3 minutes, a cooling operation starts
forcedly.
Check cool air starts blowing. If the operation does
not start, check wiring again.
2. To stop a test operation, push TEMPORARY
button once again (Approx. 1 second).
• Check wiring / piping of the indoor and outdoor
units in forced cooling operation.
TEMPORARY button
– 143 –

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents