Performance Curves - Haier AU422XIBAA Service Manual

5hp fixed frequency free multi
Hide thumbs Also See for AU422XIBAA:
Table of Contents

Advertisement

PERFORMANCE CURVES

Cooling capacity chart (kW) (change with the temperature)
AU422XIBAA
Indoor temp.
D.B. / W.B.
18
11.6
18/14
12.0
20/15
12.4
22/16
13.3
25/18
13.8
27/19
15.4
30/22
16.0
32/23
Power consumption chart (kW) (change with the temperature)
AU422XIBAA
Indoor temp.
D.B. / W.B.
18
4.0
18/14
4.0
20/15
4.1
22/16
4.1
25/18
4.2
27/19
4.4
30/22
4.5
32/23
High drop and long pipe: capacity modification curves
The data is measured in the normal condition: outdoor DB/WB 35/24, indoor DB/WB 27/19
15
12.5
10
7.5
5
2.5
0
-2.5
-5
-7.5
-10
0
Equivalent total distance between indoor and outdoor unit of one way (m).
20
25
11.4
10.9
11.7
11.4
12.1
11.7
12.9
12.7
13.4
13.2
15.0
14.5
15.5
15.1
20
25
4.1
4.2
4.1
4.2
4.2
4.2
4.3
4.3
4.4
4.4
4.5
4.6
4.6
4.6
AU422XIBAA
94%
100%
98%
96%
5
7.5
10
12.5
The standard installation piping length and drop should within this range.
Outdoor temp.
32
35 /24
10.4
9.8
10.9
10.2
11.5
11.0
12.3
11.8
12.9
12.5
14.1
13.6
14.5
14.0
Outdoor temp.
32
35 /24
4.5
4.7
4.6
4.7.
4.6
4.8
4.7
4.9
4.8
5.0
5.0
5.2
5.0
5.2
92%
88%
90%
15
17.5
20
40
43
9.3
8.8
9.8
9.3
10.1
9.8
11.0
10.7
11.4
11.1
12.7
12.3
13.3
12.8
40
43
5.1
5.3
5.1
5.4
5.2
5.4
5.3
5.6
5.4
5.6
5.6
5.8
5.7
5.9
46
8.4
8.8
9.3
10.2
10.7
11.8
12.2
46
5.5
5.6
5.7
5.8
5.9
6.1
6.2

Hide quick links: