12.5.5 Communication command and data item table
MEWTOCOL
command code
RD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
RD/WD
Data item
Use in the system
DT00100
(Never use WD command. If WD
command is sent to the KT4H/B,
the KT4H/B may not be operable.)
DT00102
SV
DT00106
Auto-tuning/Auto-reset
DT00108
OUT1 proportional band
DT00110
OUT2 proportional band
DT00112
Integral time
DT00114
Derivative time
DT00116
OUT1 proportional cycle
DT00118
OUT2 proportional cycle
DT00122
Alarm 1 value
DT00124
Alarm 2 value
DT00130
Heater burnout alarm value
DT00136
Set value lock
DT00142
Sensor correction
DT00144
Overlap band/Dead band
DT00148
Scaling high limit
DT00150
Scaling low limit
DT00152
Decimal point place
DT00154
PV filter time constant
DT00156
OUT1 high limit
DT00158
OUT1 low limit
DT00160
OUT1 ON/OFF action hysteresis
DT00162
OUT2 action mode
DT00164
OUT2 high limit
DT00166
OUT2 low limit
DT00168
OUT2 ON/OFF action hysteresis
DT00170
Alarm 1 type
DT00172
Alarm 2 type
DT00174
Alarm 1 hysteresis
DT00176
Alarm 2 hysteresis
DT00182
Alarm 1 action delayed timer
DT00184
Alarm 2 action delayed timer
Set value, Decimal point ignored
0000H: Cancel
0001H: Perform
Set value, Decimal point ignored
Set value, Decimal point ignored
Set value
Set value
Set value
Set value
Set value, Decimal point ignored
Set value, Decimal point ignored
Set value, Decimal point ignored
0000H: Unlock
0001H: Lock 1
0002H: Lock 2
0003H: Lock 3
Set value, Decimal point ignored
Set value
Set value, Decimal point ignored
Set value, Decimal point ignored
0000H: xxxx
0001H: xxx.x
0002H: xx.xx
0003H: x.xxx
Set value, Decimal point ignored
Set value
Set value
Set value, Decimal point ignored
0000H: Air cooling
0001H: Oil cooling
0002H: Water cooling
Set value
Set value
Set value, Decimal point ignored
0000H: No alarm action
0001H: High limit alarm
0002H: Low limit alarm
0003H: High/Low limits alarm
0004H: High/Low limit range alarm
0005H: Process high alarm
0006H: Process low alarm
0007H: High limit alarm with standby
0008H: Low limit alarm with standby
0009H: High/Low limits with standby
The same as the Alarm 1 type
Set value, Decimal point ignored
Set value, Decimal point ignored
Set value
Set value