10.2 Outdoor Unit

10.2.1
Selecting the Installation Location
Before choosing the installation site, obtain user
approval.
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
There should not be any animal or plant which
could be affected by hot air discharged.
Keep the spaces indicated by arrows from the wall,
ceiling, fence or other obstacles.
Do not place any obstacles which may cause a
short circuit of the discharged air.
If piping length is over the [piping length for
additional gas], additional refrigerant should be
added as shown in the table.
10.2.1.1
Installation diagram
10.2.2
Installing the Outdoor Unit
After selecting the best location, start installation
to Indoor/Outdoor Unit Installation Diagram.
1
Fix the unit on concrete or rigid frame firmly
and horizontally by bolt nut (ø10 mm).
2
When installing at roof, please consider strong
wind and earthquake.
Please fasten the installation stand firmly with
bolt or nails.
Example: For E9***
If the unit is installed at 10 m distance, the quantity of
additional refrigerant should be 50 g .... (10-7.5) m x
20 g/m = 50 g.
Model
A
E9***
570 mm
E12***
540 mm
E18***
613 mm
36
B
C
105 mm
18.5 mm
320 mm
160 mm
18.5 mm
330 mm
131 mm
16 mm
360.5 mm
D