Locating The Appliance; Correct Vent Distance From Outside Wall Or Roof Termination - Laars MASCOT LX Installation And Operation Instructions Manual

Hide thumbs Also See for MASCOT LX:
Table of Contents

Advertisement

Mascot LX Boilers and Water Heaters
SECTION 2.

Locating the Appliance

2.1 Locating the Appliance
The Mascot LX is designed for indoor
wall-mounted installations only.
The Mascot LX must be mounted to a suitable wall by
a qualified heating contractor under the guidelines of a
wall mounted boiler or combination unit. Use a suitable
wall, either concrete or wood and use the appropriate
fasteners for that wall. Failure to wall mount this boiler
using correct fasteners will affect the performance and
life expectancy of the boiler and will void the warranty.
The appliance should be located to provide clearances
on all sides for maintenance and inspection. It should
not be located in an area where leakage of any
connections will result in damage to the area adjacent to
the appliance, the wall that it is hung on, or to the lower
floors of the structure.
When such a location is not available, it is recommended
that a suitable drain pan, adequately drained, be installed
under the appliance.
The appliance is design certified by CSA-International
for wall-mounted installation in basements; in closets,
utility rooms or alcoves. The location for the appliance
should be chosen with regard to the vent pipe lengths
and external plumbing and on a plumb (vertical) wall.
The unit shall be installed such that the gas ignition
system components are protected from water (dripping,
spraying, rain, etc.) during operation and service
(circulator replacement, control replacement, etc.).
If the vent terminal and/or combustion air terminal
terminate through a wall, and there is potential for snow
accumulation in the local area, both terminals must
be installed at an appropriate level above grade or the
maximum expected snow line.
The dimensions and requirements that are shown in
Table 3
should be met when choosing the locations for
the appliance.
2.2 Correct Vent Distance from Outside
Wall or Roof Termination
The forced draft combustion air blower in the appliance
has sufficient power to vent properly when the
guidelines in Table 4 are followed.
For concentric vent terminal kit (optional), follow
installation instructions included with the kit.
Sizing Data
Model
MLX
50
MLX
75
100 100,000 29.3
MLX
MLX
125 125,000 36.6
MLX
150 150,000 43.9
MLX
175 175,000 51.6
MLX
220 220,000 64.4
NOTES:
1. For other boiler ratings:
Boiler Horsepower: HP = Output
Sizing Data,
Piping
Figure 7. Locating the Appliance.
APPLIANCE
Clearances
SURFACE
Left Side
Right Side
Top
Closet, Front
Front
Bottom
Vent
Table 3.
NOTE: When located on the same wall, the Minimum
Venting Distance is found on
12
30
Input
Output
BTU/h
kW
BTU/h
50,000
47,500
14.6
13.2
75,000
71,250
21.9
20.8
95,000
27.8
118,750
34.8
142,500
41.8
166,250
48.7
209,000
61.2
Radiation Surface: EDR sq. ft. = Output
33,475
Cond.
Hydronic
Outlet
Return
3/4"
50 thru 125
PVC
copper
3/4"
150 - 220
PVC
SUGGESTED SERVICE ACCESS CLEARANCE
INCHES
Certifi ed by CSA for zero clearance to
combustible materials on all sides.
Clearances
Figure
Page 7
DHW
AFUE
Gas
Output @
Conn. Size Conn
kW
75°F Rise
inches
-
95% 1/2" NPT
-
95% 1/2" NPT
-
95% 1/2" NPT
3.1 gpm
95% 1/2" NPT
3.7 gpm
95% 1/2" NPT
4.3 gpm
95% 1/2" NPT
-
95% 1/2" NPT
150
DHW
2nd
Inlet
Return
3/4"
1/2"
3/4"
NPT
copper
1"
1/2"
3/4"
NPT
NPT
copper
CM
6
15
6
15
12
30
6
15
24
61
24
61
1
3
11.
Wa
inch
3/4"
3/4"
3/4"
3/4"
1" N
1" N
1" N
Gas
Supply
1/2"
NPT
1/2"
NPT

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents