Standard Supplied Accessories; Optional Accessories; Technical And Electrical Specifications; Main Components - Daikin CMSQ200A7W1B Installation Manual

Hide thumbs Also See for CMSQ200A7W1B:
Table of Contents

Advertisement

1.2.

Standard supplied accessories

See location 1 in
figure 17
accessories are supplied with the unit.
Item
Installation manual
Operation manual
Additional refrigerant charge label
Fluorinated greenhouse gases label
Multilingual fluorinated greenhouse gases label
See location 2 in
figure 17
accessories are supplied with the unit.
Gas side accessory pipe
Item
Liquid side accessory pipe
Item
1.3.

Optional accessories

To install the above outdoor units, the following optional parts are
also required.
Refrigerant branching kit (for R410A only: Always use an
appropriate kit dedicated for your system.)
Refnet header
KHRQ22M29H
1.4.
Technical and Electrical specifications
Refer to the Engineering Data Book for the complete list of
specifications.
2.
M
AIN COMPONENTS
For main components and function of the main components, refer to
the Engineering Data Book.
Installation manual
2
for reference to where following
Quantity
1
1
1
1
1
for reference to where following
Quantity
1
1
Quantity
1
1
Refnet joint
KHRQ22M20T
KHRQ22M29T9
3.
S
ELECTION OF LOCATION
This unit, both indoor and outdoor, is suitable for installation in a
commercial and light industrial environment. If installed as a house-
hold appliance it could cause electromagnetic interference, in which
case the user may be required to take adequate measures.
Make sure to provide for adequate measures in order
to prevent that the outdoor unit be used as a shelter
by small animals.
Small animals making contact with electrical parts can
cause malfunctions, smoke or fire. Please instruct the
customer to keep the area around the unit clean.
Obtain the customer's permission before installing.
The inverter units should be installed in a location that meets the
following requirements:
1
The foundation is strong enough to support the weight of the unit
and the floor is flat to prevent vibration and noise generation.
If not, the unit may fall over and cause damage or
injury.
2
The space around the unit is adequate for servicing and the
minimum space for air inlet and air outlet is available. (Refer to
figure 1
and choose one of the possibilities).
A B C D
Sides along the installation site with obstacles
Suction side
■ In case of an installation site where sides A+B+C+D have
obstacles, the wall heights of sides A+C have no impact on
service space dimensions. Refer to
heights of sides B+D on service space dimensions.
■ In case of an installation site where only the sides A+B have
obstacles, the wall heights have no influence on any
indicated service space dimensions.
NOTE
The service space dimensions in
based on cooling operation at 35°C.
3
Make sure that there is no danger of fire due to leakage of
inflammable gas.
4
Ensure that water can not cause any damage to the location in
case it drips out the unit (e.g. in case of a blocked drain pipe).
5
The piping length between the outdoor unit and the indoor unit
may not exceed the allowable piping length. (Refer to
"6.6. Example of connection" on page
6
Select the location of the unit in such a way that neither the
discharged air nor the sound generated by the unit disturbs
anyone.
7
Make sure that the air inlet and outlet of the unit are not
positioned towards the main wind direction. Frontal wind will
disturb the operation of the unit. If necessary, use a windscreen
to block the wind.
8
Do not install or operate the unit on locations where air contains
high levels of salt, like e.g. in the vicinity of oceans. (Refer for
further information to the engineering databook).
9
During installation, avoid the possibility that anybody can climb
on the unit or place objects on the unit.
Falls may result in injury.
10 When installing the unit in a small room, take measures in order
to keep the refrigerant concentration from exceeding allowable
safety limits in the event of a refrigerant leak.
Excessive refrigerant concentrations in a closed room
can lead to oxygen deficiency.
11 The equipment is not intended for use in a potentially explosive
atmosphere.
figure 1
for impact of wall
figure 1
are
7)
CMSQ200+250A7W1B
Air conditioning system
4PW47543-1C – 07.2010

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cmsq250a7w1b

Table of Contents