[DESIGN PRESSURE]
• As the design pressure for local connection piping (suction·HP/LP
gas pipe, gas pipe, and liquid pipe) is at least 3.3 MPa, it is pos-
sible to use existing piping (design pressure of at least 3.3 MPa)
but refer to "6. REFRIGERANT PIPING" and check that existing
piping (including branch piping) is compatible with this unit in
terms of materials and thickness and that it does not appear to be
corroded.
Air tight test (3.3 MPa 24/h) to check the strength of existing pip-
ing and that it has no gas leaks.
If it is not possible to perform a pressure test, place existing piping
with piping rated at least 3.3 MPa.
• Check that there has been no compressor malfunction, gas sup-
ply exhaustion, or similar issues that could be attributable to pipe
problems in the past. If there have been any such problems,
check that appropriate repairs were made, and if not, implement
such repairs.

1-3 Disposal requirements

Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with relevant local and national
legislation.
2.

INTRODUCTION

• VRVIII-Q series are designed for outdoor installation and used for
cooling and heat pump applications. Outdoor units come in three
standard sizes, and with a single system through a multi system
combining up to three outdoor units (Heat Pump series), and up to
four outdoor units (Heat Recovery series). Rated capacity is
below.
RQ(C)YQ: Cooling 14.0~54.0 kW, Heating 16.0~60.0 kW
RQCEQ: Cooling 28.0~84.8 kW, Heating 32.0~89.6 kW
• The BS units that combined with RQCEQ system for changing the
refrigerant flow to indoor units are BSVQ100,160, 250P,
BSV4Q100P and BSV6Q100P type only. Conmbination with
other BS type units will cause malfunction.
• The VRV units can be combined with Daikin VRV series indoor
units for air conditioning purposes. Always use appropriate indoor
units compatible with R410A. To learn which models of indoor
units are compatible with R410A, refer to the product catalogs.
Combination with other indoor refrigerant units will cause malfunc-
tion.

2-1 Combination

The indoor units can be installed in the following range.
• Heat Pump series (RQ(C)YQ)
<Outdoor unit>
<Total capacity of indoor units> <Total quantity of indoor units>
RQYQ140PY1 ....................7.0 ~ 18.2
RQYQ180PY1 ....................9.0 ~ 23.4
RQCYQ280PY1............... 14.0 ~ 36.4
RQCYQ360PY1................17.8 ~ 46.2
RQCYQ460PY1................22.5 ~ 58.5
RQCYQ500PY1................25.0 ~ 65.0
RQCYQ540PY1................28.0 ~ 72.8
• Heat Recovery series (RQCEQ)
<Outdoor unit>
<Total capacity of indoor units> <Total quantity of indoor units>
RQCEQ280PY1................14.0 ~ 36.4
RQCEQ360PY1................17.8 ~ 46.2
RQCEQ460PY1................22.5 ~ 58.5
RQCEQ500PY1................25.0 ~ 65.0
RQCEQ540PY1................28.0 ~ 72.8
RQCEQ636PY1................30.8 ~ 80.0
RQCEQ712PY1................34.5 ~ 89.7
RQCEQ744PY1................36.5 ~ 94.9
RQCEQ816PY1................40.0 ~ 104
RQCEQ848PY1................42.5 ~ 111
Note
• Be sure to connect an R410A indoor unit.
See the catalog for indoor unit models which can be connected.
• Above is the total capacity and total number of units of the indoor
units when configured in a standard combination. See the techni-
cal reference for details on total capacity and total number of
indoor units when using a configuration other than the standard
combination. The standard combinations are as follows.
3
• Heat Pump series (RQ(C)YQ)
<Combination unit>
RQYQ140PY1
RQYQ180PY1
RQCYQ280PY1
RQCYQ360PY1
RQCYQ460PY1
RQCYQ500PY1
RQCYQ540PY1
• Heat Recovery series (RQCEQ)
<Combination unit>
RQCEQ280PY1
RQCEQ360PY1
RQCEQ460PY1
RQCEQ500PY1
RQCEQ540PY1
RQCEQ636PY1
RQCEQ712PY1
RQCEQ744PY1
RQCEQ816PY1
RQCEQ848PY1
Note
• Combinations other than those above are prohibited.
• If the total capacity of the connected indoor units exceeds the
capacity of the outdoor unit, cooling and heating performance
may drop when running the indoor units. See the capacity table in
the Engineering Data Book for details.
• There are restrictions on the refrigerant pipe connecting order
between outdoor unit in the case of the multi system.
Install so that the following restrictions are satisfied.
<Restrictions>
The capacities of outdoor units A and B must fulfill the following
conditions.
A ≥ B
Outdoor unit multi
connection
piping kit

2-2 Standard supplied accessories

8 units
The following accessories are included. The storage location of the
10 units
accessories is shown in figure 1.
16 units
20 units
• Heat Pump series (RQYQ)
26 units
29 units
Name
33 units
Quantity
16 units
20 units
26 units
Shape
29 units
33 units
36 units
40 units
Name
43 units
Quantity
47 units
50 units
Shape
<Independent unit>
RQYQ140PY1
RQYQ180PY1
RQYQ140PY1+RQYQ140PY1
RQYQ180PY1+RQYQ180PY1
RQYQ180PY1+RQYQ140PY1+RQYQ140PY1
RQYQ180PY1+RQYQ180PY1+RQYQ140PY1
RQYQ180PY1+RQYQ180PY1+RQYQ180PY1
<Independent unit>
RQEQ140PY1+RQEQ140PY1
RQEQ180PY1+RQEQ180PY1
RQEQ180PY1+RQEQ140PY1+RQEQ140PY1
RQEQ180PY1+RQEQ180PY1+RQEQ140PY1
RQEQ180PY1+RQEQ180PY1+RQEQ180PY1
RQEQ212PY1+RQEQ212PY1+RQEQ212PY1
RQEQ212PY1+RQEQ180PY1+RQEQ180PY1+RQEQ140PY1
RQEQ212PY1+RQEQ212PY1+RQEQ180PY1+RQEQ140PY1
RQEQ212PY1+RQEQ212PY1+RQEQ212PY1+RQEQ180PY1
RQEQ212PY1+RQEQ212PY1+RQEQ212PY1+RQEQ212PY1
Outdoor
unit A
to indoor unit
Gas side
Gas side
Liquid side
accessory
accessory
accessory
pipe (1)
pipe (2)
pipe (1)
1 pc.
1 pc.
1 pc.
(Long)
(Short)
Clamp (1) Clamp (2) Clamp (3)
1 pc.
8 pcs.
1 pc.
(Large)
(Small)
Outdoor
unit B
Liquid side
L type
accessory
accessory
pipe (2)
joint
1 pc.
1 pc.
Others
1 pc. each item
• Operation manual
• Installation manual
• Declaration confor-
mity (PED, EMC,
MD)
• "REQUEST FOR
THE INDICATION"
label (Installation
records)
• "ADDITIONAL REF.
CHARGE" label
English