Installation Instructions

READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION
These instructions cover the basic principles to ensure satisfactory installation of the stove, although detail
may need slight modification to suit particular local site conditions. In all cases the installation must comply
with National and European Building Regulations, Local Authority Byelaws and other specifications or
regulations as they affect the installation of the stove.
Health and Safety Precautions
Handling
Adequate facilities must be available for unloading and site handling.
Fire Cement
Some types of fire cement are caustic and should not be allowed to come into contact with the
skin. In case of contact, wash immediately with plenty of water.
Asbestos
This stove contains no asbestos. If there is a possibility of disturbing any asbestos in the course
of installation then please seek specialist guidance and use appropriate protective equipment.
Metal Parts
When installing or servicing this stove, care should be taken to avoid the possibility of personal
injury.
Please note:
Any white deposits on the stove joints are caused by humidity reacting with the joint sealant.
These deposits may be brushed off and, if necessary, blackened with a proprietary stove polish.
Important Warning
This stove must not be installed into a chimney that serves any other heating appliance.
No purpose provided ventilation is required for stoves rated under 5KW. For each KW above
5KW, 550 sq mm of fixed ventilation is required – i.e. a stove rated at 8KW would require 3 x
550 sq mm = 1650 sq mm of fixed ventilation. If more than one appliance is installed in the same
room, the ventilation requirements for each appliance must be added together.
There must not be an extractor fan fitted in the same room as the stove as this can cause the stove
to emit fumes into the room.
Installation
Chimney
The chimney height and the position of the chimney terminal should conform to Building
Regulations. Check that the chimney is in good condition, dry, free from cracks and obstructions.