Mitsubishi Electric City Multi PUHY-RP-YJM-B Installation Manual page 4

For building application outdoor unit
Table of Contents

Advertisement

9
A
Unit combination
Å Outdoor model
unit1
unit2
RP200
-
-
RP250
-
-
RP300
-
-
RP350
-
-
RP400
RP200
RP200
RP450
RP200
RP250
RP500
RP250
RP250
RP550
RP250
RP300
RP600
RP300
RP300
RP300
RP350
RP650
RP700
RP200
RP250
RP750
RP250
RP250
RP250
RP250
RP800
RP850
RP250
RP300
RP900
RP300
RP300
*1 The pipe sizes listed in columns A1 to A3 in this table correspond to the
sizes for the models listed in the unit 1, 2, and 3 columns. When the order
of the models for unit 1, 2, and 3 change, make sure to use the appropriate
pipe size.
*2 ø25.4 for R22
B, C, D
Î Total capacity of indoor units
~ 80
81 ~ 160
161 ~ 330
331 ~ 480
481 ~ 630
631 ~
a, b, c, d, e
‰ Model number
ı Liquid pipe
15,20,25,32,40
50,63,71,80
100,125,140
200,250
Ï Downstream unit model total
~ 200
201 ~ 400
401 ~ 650
Ó The 1st branch of P450 ~ P650
651 ~
È The 1st branch of P700, P750, P800
4
A
ı Liquid pipe
Ç Gas pipe
unit3
-
ø12.7
ø28.58*2
-
ø12.7
ø28.58
-
ø12.7
ø28.58
-
ø15.88
ø34.93
-
ø15.88
ø34.93
-
ø15.88
ø34.93
-
ø15.88
ø34.93
-
ø15.88
ø34.93
-
ø19.05
ø34.93
-
ø19.05
ø41.28
RP250
ø19.05
ø41.28
RP250
ø19.05
ø41.28
RP300
ø19.05
ø41.28
RP300
ø19.05
ø41.28
RP300
ø19.05
ø41.28
(mm)
ı Liquid pipe
Ç Gas pipe
ø9.52
ø15.88
ø12.7
ø19.05
ø12.7
ø25.4 or ø28.58
ø15.88
ø31.75 or ø34.93
ø15.88
ø38.1 or ø34.93
ø19.05
ø41.28
(mm)
Ç Gas pipe
ø6.35
ø12.7
ø9.52
ø15.88
ø9.52
ø19.05
ø12.7
ø28.58
Ì Joint
CMY-Y102SS-G2
CMY-Y102LS-G2
CMY-Y202S-G2
CMY-Y302S-G2
9.2
A1 *1
A2 *1
ı Liquid pipe
Ç Gas pipe
ı Liquid pipe
Ç Gas pipe
-
-
-
-
-
-
-
-
-
-
-
-
ø9.52
ø19.05
ø9.52
ø9.52
ø19.05
ø9.52
ø9.52
ø22.2
ø9.52
ø9.52
ø22.2
ø12.7
ø12.7
ø22.2
ø12.7
ø12.7
ø22.2
ø12.7
ø9.52
ø19.05
ø9.52
ø9.52
ø22.2
ø9.52
ø9.52
ø22.2
ø9.52
ø9.52
ø22.2
ø12.7
ø12.7
ø22.2
ø12.7
Ô 4-Branching header
(Downstream unit
model total = 200)
CMY-Y104-G
Å Outdoor model
P400 ~ P650
P700 ~ P900
A3 *1
ı Liquid pipe
Ç Gas pipe
ı Liquid pipe
-
-
-
-
-
-
-
-
-
-
-
-
ø19.05
-
-
ø22.2
-
-
ø22.2
-
-
ø22.2
-
-
ø22.2
-
-
ø28.58
-
-
ø22.2
ø9.52
ø22.2
ø19.05
ø22.2
ø9.52
ø22.2
ø19.05
ø22.2
ø12.7
ø22.2
ø19.05
ø22.2
ø12.7
ø22.2
ø19.05
ø22.2
ø12.7
ø22.2
ø19.05
Ò 10-Branching header
8-Branching header
(Downstream unit
(Downstream unit
model total = 400)
model total = 650)
CMY-Y108-G
CMY-Y1010-G
˜ Outdoor twinning kit
CMY-RP100VBK
CMY-RP200VBK
(mm)
A4
Ç Gas pipe
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
ø34.93
ø34.93
ø34.93
ø34.93
ø34.93

Advertisement

Table of Contents
loading

This manual is also suitable for:

City multi puhy-rp-yjm-b-bs

Table of Contents