12. Test run

12.1. The following phenomena do not represent faults.

Phenomenon
Indoor unit does not perform cooling (heating)
operation.
The auto vane rotates and begins to blow air
horizontally.
Fan setting changes during heating.
Fan stops during heating operation.
Fan does not stop while operation has been
stopped.
No setting of fan while start SW has been
turned on.
Indoor unit remote controller shows "H0" or
"PLEASE WAIT" indicator for about five min-
utes when turning ON universal power sup-
ply.
Drain pump does not stop when unit is
stopped.
Drain pump continues to operate while unit
has been stopped.
Indoor unit emits noise when switching from
heating to cooling and vice versa.
Immediately after startup, the indoor unit
emits the sound of the refrigerant flow.
Warm air comes from an indoor unit that is
not performing a heating operation.

13. Information on rating plate

Model
RP200
Unit combination
-
Refrigerant
6.5
Allowable pressure (Ps)
HP: 4.15MPa , LP: 2.21MPa
Net weight
230kg
Model
RP400
Unit combination
RP200
Refrigerant
6.5
Allowable pressure (Ps)
Net weight
230kg
Model
RP700
Unit combination
RP200
Refrigerant
6.5
Allowable pressure (Ps)
Net weight
230kg
MANUFACTURER: MITSUBISHI ELECTRIC CORPORATION
AIR-CONDITIONING & REFRIGERATION SYSTEMS WORKS 5-66, TEBIRA, 6-CHOME, WAKAYAMA CITY, JAPAN
Display of remote controller
"Cooling (heating)" flashes
Normal display
Normal display
Defrost display
No lighting
Heat ready
"H0" or "PLEASE WAIT" flashes
Light out
Normal display
Normal display
Normal display
RP250
RP300
RP350
-
-
-
9.0
9.0
9.0
255kg
255kg
255kg
RP450
RP500
RP200
RP200
RP250
RP250
6.5
6.5
9.0
9.0
HP: 4.15MPa , LP: 2.21MPa
230kg
230kg
255kg
255kg
RP750
RP250
RP250
RP250
RP250
9.0
9.0
9.0
9.0
255kg
255kg
255kg
255kg
When another indoor unit is performing the heating (cooling) operation, the cool-
ing (heating) operation is not performed.
If air has been blowing downward for 1 hour during cooling, the unit may
automatically change to horizontal blowing with the control operation of the auto
vane. During defrosting or immediately after heating start-up/shut-down, the auto
vane automatically rotates to blow air horizontally for a short period of time.
Ultra-low speed operation is commenced at thermostat OFF.
Light air automatically changes over to set value by time or piping temperature at
thermostat ON.
The fan is to stop during defrosting.
The fan is set to run for 1 minute after stopping to exhaust residual heat (only in
heating).
Ultra low-speed operation for 5 minutes after SW ON or until piping temperature
becomes 35°C, low speed operation for 2 minutes thereafter, and then set notch
is commenced (Hot adjust control).
The system is being started up.
Operate remote controller again after "H0" or "PLEASE WAIT" disappear.
After cooling operation stops, the unit continues to operate drain pump for three
minutes and then stops it.
Unit continues to operate drain pump if drainage is generated, even during a
stop.
This is a switching sound of the refrigerant circuit and does not imply a problem.
Unstable flow of the refrigerant emits a sound. This is temporary and does not
imply a problem.
The LEV is slightly open to prevent refrigerant, of the indoor unit that is not
performing the heating operation, from being liquefied. This does not imply a
problem.
RP550
RP600
RP250
RP250
RP300
RP300
9.0
9.0
9.0
9.0
255kg
255kg
255kg
255kg
RP800
RP250
RP250
RP250
RP300
9.0
9.0
9.0
9.0
HP: 4.15MPa , LP: 2.21MPa
255kg
255kg
255kg
255kg
Cause
RP650
RP300
RP300
RP350
9.0
9.0
9.0
255kg
255kg
255kg
RP850
RP250
RP300
RP300
RP300
9.0
9.0
9.0
9.0
255kg
255kg
255kg
255kg
RP900
RP300
RP300
9.0
9.0
255kg
255kg
21