1. Mount the device on a DIN rail inside an approved
enclosure.
2. Connect a single phase feed to the supply terminals.
This device must be earthed.
3. Connect KNX TP1 bus cables. Ensure correct cable
type and lengths. Ensure required cable segregation to
other circuits.
4. Connect Aux Supply cables if required. Ensure correct
polarity and required segregation to other circuits.
5. Re-check all terminations prior to energizing and
energize the supply.
6. Check supply, KNX bus voltage and Aux supply using
a multimeter. Load supply shall be within the load
specification, KNX bus shall be between 21-30Vdc,
Aux supply shall be between 24-30Vdc.

Product Specifications

Supply
120-250V 50/60Hz at 0.5A
Output
640mA @ 29Vdc for direct KNX BUS supply
Protection
Overload protection
Short circuit proof
Supply Terminals
Line, Neutral, Earth Screw Terminal
1 x 1.5mm
max conductor size
2
Output Terminals
Wago 243 (Red/Grey) for KNX Bus
Wago 243 (Yellow/White) for auxiliary supply
0.6-0.8mm wire diameter single core KNX cable
Warranty Policy
Philips warrant to the original purchaser for a period of twenty four (24) months from the date of shipment ex-factory of the equipment that should the equipment prove defective by
reason of improper workmanship or material, Philips will repair or replace the same without charge provided the equipment has not been improperly installed, operated, repaired, damaged
or abused. The warranty granted herein is limited to repair or replacement only. Philips has the right to substitute any warranty item not on the current price/equipment list. As far as the law
permits, Philips shall not be liable for any loss or damage caused to property or persons arising from any cause whatsoever. This warranty is subject to the return of the equipment to Philips,
or the Philips authorised distributor who supplied the equipment (the 'Supplier'), by prepaid freight within the twenty four (24) months warranty period. Where Philips, or the Supplier, agree
to a site visit during the warranty period and it is found to be an operational problem, and not subject to warranty in that event, then a field service call out charge will apply. Contact Philips
or the Supplier for details.
PPS640-KNX Installation Manual
Rev A March 2012
Specifications subject to change without notice.
© Not to be reproduced without permission.
Unit 6, 691 Gardeners Road Mascot 2020 Australia.
ABN 33 097 246 921
Connecting KNX Data Cabling
Connect Data Cable in a Daisy Chain
KNX Bus Permanent Connections
Compliance
CE, KNX
Operating Environment
-5° to 45°C ambient temperature
0% to 90% RH non condensing
Construction
Plastic enclosure
Dimensions
6 Pole: H107mm x W91mm x D62mm