Toshiba RAV-SM564UTP-E Installation Manual page 17

Air conditioner (split type) 4-way cassette type
Hide thumbs Also See for RAV-SM564UTP-E:
Table of Contents

Advertisement

 How to set up louver lock
(No swing)
1. Push
(right side of the button) for at least
four seconds when the air conditioner is not working.
flashes.
Indicates CODE No. [F1].
2. Select an indoor unit to be set by pushing
(left side of the button).
Each time you push the button, unit numbers
change as follows:
The fan of the selected unit runs and the louvers
start swinging.
UNIT No.
UNIT No.
UNIT No.
1-1
1-2
1-3
UNIT No.
1-4
3. Select a louver you want to lock by pushing "TEMP."
buttons.
4. Select the wind direction of the louver you do not
want to swing by pushing "TIME"
(1)
(2)
(3)
SET DATA
0001
0002
0003
(4)
(5)
0004
0005
* When (4) or (5) is selected, dew drop may occur
during cooling mode.
5. Determine the setting by pushing
button.
When the setting has been determined,
up.
6. Push
button to complete the setting.
0001-0005
(Louver lock position code)
31-EN
 How to cancel louver lock
Set the wind direction to "0000" of the louver lock setup
procedure above.
Setting data
0000
• When the setting is canceled,
Other operations are the same as those in "How
to set up louver lock (No swing)".
 Remote controller sensor
The temperature sensor of the indoor unit senses room
temperature usually. Set the remote controller sensor
to sense the temperature around the remote controller.
Select items following the basic operation procedure
buttons.
1
2
3
4
5
6
(
).
• Specify [32] for the CODE No. in Procedure
• Select the following data for the SET DATA in
4
Procedure
.
SET DATA
0000
Remote controller
Not used
sensor
(factory default)
When
flashes, the remote controller sensor is
defective.
Select the SET DATA [0000] (not used) or replace the
remote controller.
lights
 Power saving mode
Performing settings of the power saving
mode
* When an outdoor unit RAV-SP***2AT / SM***3AT
type or earlier is used, the power level is fixed to 75
% regardless of the value on the display.
1
Push
when the air conditioner is not working.
flashes.
Indicates CODE No. "C2."
goes out.
2
Select an indoor unit to be set by pushing
(left side of the button).
Each time the button is pushed, unit numbers
change as follows:
UNIT No.
1-1
The fan of the selected unit runs.
3
3
.
Adjust the power save setting by pushing
TIME
Each push of the button changes the power level
by 1% within the range from 100 % to 50 %.
0001
*The factory default is 75 %.
Used
4
Determine the setting by pushing
5
Push
button to complete the setting.
– 16 –
 Remote controller switch
monitoring function
This function is available to call the service monitor
mode from the remote controller during a test run to
acquire temperatures of sensors of the remote
controller, indoor unit, and outdoor unit.
button for 4 seconds or more
2
4
UNIT No.
UNIT No.
1-2
1-3
UNIT No.
1
1-4
Push
at least 4 seconds to call the service monitor
mode.
The service monitor indicator lights up and the
buttons.
header indoor unit number is displayed first.
CODE No.
2
Pushing TEMP.
number of sensor (CODE No.) to be
monitored. (See the following table.)
3
Pushing
select an indoor unit to be monitored. The
sensor temperatures of indoor units and
their outdoor unit in the control group are
displayed.
Setting of power level in
power saving mode
button.
1
3
and
buttons simultaneously for
is also displayed.
buttons, select the
(left side of the button),
32-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents