MQRB6961 Single Sided Framing

An MQRB6961BK Kit is required for a Single Sided Installation.
Before you begin Framing- Determine whether the Wall Surface will be flush with the face of the fireplace (Fireplace
Note: If using optional surround, maximum thickness for non-combustible material is 3/4".
Framed Opening 71-1/2" x 45-1/2"
Framing Style shown is for illustration purposes only.
This structure is NOT load bearing.
*21" Min.
Dimension is for Wall Surface Flush with fireplace.
Add 1/2" to this Dimension where a non-combustible wall surface will
cover the unit (See Nailing Tab Guide Page also).
Fireplace vent MUST maintain min. 1" clearance from combustible (Wood) framing.
However, if steel stud framing is used, 1" vent clearance is not required.
and wall to be covered with Non-Combustibles, such as tile), or the Framing will be flush
with the face of the fireplace (Flat Wall appearance).
Also refer to these sections:
Clearance to Combustibles
Enclosure Heights
Venting
21" Min.*
(Continued)