1. Safety Precautions Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing. Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating and main circuit for the model installed. The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below.
Page 4
19. Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock or fire. 20. Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done, the set will drop and cause injury.
2. Specifications WH-SHF09D3E5 WH-UH09DE5 Item Unit Outdoor Unit Performance Test Condition EN14511 Condition A7W35 A2W35 (Ambient/Water) 9.00 9.00 Heating Capacity BTU/h 30700 30700 kcal/h 7740 7740 4.55 3.40 kcal/hW 3.91 2.92 dB (A) Noise Level Power Level dB Air Flow...
Page 6
Item Unit Running Current 12.7 Maximum Current For Heat Pump System 28.5 Power Factor Power factor means total figure of compressor and outdoor fan motor. Number of core Power Cord Length m (ft) Thermostat Electronic Control Protection Device Electronic Control Item Unit Indoor Unit...
WH-SHF12D6E5 WH-UH12DE5 Item Unit Outdoor Unit Performance Test Condition EN14511 Condition A7W35 A2W35 (Ambient/Water) 12.00 12.00 Heating Capacity BTU/h 41000 41000 kcal/h 10320 10320 4.40 3.23 kcal/hW 3.78 2.77 dB (A) Noise Level Power Level dB Air Flow /min (ft /min) 80.0 (2830) Refrigeration Control Device...
Page 8
Item Unit Running Current 13.0 17.4 Maximum Current For Heat Pump System 29.0 Power Factor Power factor means total figure of compressor and outdoor fan motor. Number of core Power Cord Length m (ft) Thermostat Electronic Control Protection Device Electronic Control Item Unit Indoor Unit...
3. Features Inverter Technology - Energy saving High Efficiency Compact Design Environment Protection - Non-ozone depletion substances refrigerant (R407C) Long Installation Piping - Long piping up to 30 meter with height difference 20 meter - Flexible 4-way piping for outdoor unit Easy to use control panel Weekly Timer setting Quality Improvement...
6. Refrigeration and Water Cycle Diagram Piping size Min. Max. Rated Common Additional Piping Piping Model Length Length Elevation Refrigerant Liquid Length Length (g/m) UH09DE5 5/8” 3/8” UH12DE5 5/8” 3/8” * If piping length is over common length, additional refrigerant should be added as shown in the table.
11. Installation Instruction 11.1 Select the Best Location Indoor Unit Piping size Addi- Min. Max. There should not be any heat source or steam Rated tional Eleva- Piping Piping Model Length Refrige- near the unit. tion Length Length Gas Liquid rant A place where air circulation in the room is good.
11.3 Indoor Unit 11.3.1 How to Fix Installation Plate 11.3.3 Indoor Unit Installation The mounting wall is strong and solid enough to prevent it from vibration. 11.3.3.1 Install the Indoor Unit When connecting solar pump station cable between indoor unit and solar pump station, the distance between both apparatuses shall be 2 ~ 8 meters and the length of the said cable must be shorter than 10 meter.
Page 33
11.3.3.3 Indoor Unit Refrigerant Pipe Install external filter (30 mesh or more, field supply) before water inlet of indoor unit (with “WATER IN” Installation indication). Please make flare after inserting flare nut Refer to Diagram 4.1 for pipe connection of Panel (located at joint portion of tube assembly) onto Heater, Floor Heater, Tank Unit, Solar Pump the copper pipe.
11.3.4 Connect the Cable to the Indoor Unit Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 x 4.0 or 6.0 mm flexible cord, type designation 60245 IEC 57 or heavier cord. Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor unit’s respectively.
Page 36
11.3.4.2 Connecting Requirement The equipment’s power supply 1 complies with IEC/EN 61000-3-12 provided that the short-circuit power S greater than or equal to 1700.31kW (for SHF09D3E5/UH09DE5 and SHF12D6E5/UH12DE5) at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power S greater than or equal to 1700.31kW.
11.4 Outdoor Unit 11.4.1 Install the Outdoor Unit After selecting the best location, start installation according to Indoor/Outdoor Unit Installation Diagram. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10mm). When installing at roof, please consider strong wind and earthquake.
11.4.3 Evacuation of the Equipment WHEN INSTALLING AN AIR-TO-WATER HEATPUMP, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve.
Select required direction and apply protective bushing provided in accessories to protect cables from sharp edges. Once all wiring work has been completed, tie the cables and cord together with the binding strap so that they do not touch other parts such as the compressor and bare copper pipes. Install back the control board cover.
12. Operation and Control 12.1 Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature shifting.
Page 41
Booster heater control - Booster heater turn On and Off follow normal operation. - Booster heater turn ON condition: During startup time (initialization), Booster heater turn ON after DELAY TIMER. When tank temperature lower than HEATER ON TEMP 20 minutes from previous heater off. - Booster heater turn OFF condition: When tank temperature higher than tank set temperature for continuous 15 secs.
Page 42
Case 2: Heat pump THERMO OFF TEMP: Heat pump THERMO OFF TEMP = 63°C + [+4°C]. Water outlet temperature > Heat pump THERMO OFF TEMP for continuous 3 minutes, heat pump OFF. Next THERMO ON TEMP: THERMO ON TEMP = Water inlet when heat pump THERMO OFF + [-3°C]. If water outlet temperature <...
Page 43
- Switch to tank heat-up interval and start counting tank heat-up timer when tank temperature < THERMO ON TEMP after room heat-up interval timer complete * THERMO ON TEMP is defined form following Case1 to Case4. During tank heat-up interval - Heat pump tank target temperature = Tank set temperature or [60°C] whichever lower - Heat pump Water Outlet set temperature is set to Maximum [65°C] during tank interval - Initial Tank THERMO ON TEMP = heat pump tank target temperature + [-2°C]...
Page 44
Solar 3 way valve: Solar 3WV operates follow solar operation specification. * Under solar priority is set condition, when solar 3WV is ON, booster heater turn OFF * Under solar priority is not set condition, solar 3WV only can ON during heating heat-up interval. 2 way valve opens.
Page 45
12.1.7 Outdoor Fan Motor Operation Outdoor fan motor is adjusted according to operation condition. It starts when compressor starts operation and it stops 30 seconds after compressor stops operation.
12.2 Water Pump 12.2.1 Water Pump Control Once the indoor unit is ON, the water pump will be ON immediately and no error judgement for 9 minutes. However, during this 9 minutes operation, if there is any abnormality cause at outdoor or malfunction, the compressor should be OFF immediately and restart delay after 3 minutes.
12.3 Pump Down Operation Purpose Ensure the pump down operation when relocating or disposing of the unit. The pump down operation will extract all refrigerant from the piping into the outdoor unit. Pump down operation control: Press the SERVICE S/W for continuous 5 secs to enter Service mode. In service mode, select Sr:01 and press SET S/W to start Pump Down operation.
12.6 Indoor Unit Safety 12.6.1 Indoor Unit Safety Control When water pump is ON, the system will start checking flow switch status (ON/OFF). If the flow switch ON for 10 seconds, the system will check on the water inlet temperature for 10 seconds. If the water inlet temperature not exceeds 80°C, the water pump shall be continuously running with normal mode.
12.9 Indoor Back-Up Heater Control 12.9.1 Indoor Electric Heater Control Normal Heating Mode Heater On condition: a. Heater switch is ON b. After Heatpump thermo ON for [30] mins c. After water pump operate [9] mins d. Outdoor air temperature < Outdoor set temperature for heater e.
12.10 Tank Booster Heater Control 12.10.1 Tank Booster Heater Control Heating operation condition: Booster heater Turn On condition: After BOOSTER HEATER DELAY TIMER fulfill during heat pump startup time in tank mode, or during switching from heating heat-up interval to tank heat-up interval in heat + tank mode (heating priority not set).
12.13 Quiet Operation Purpose: - To provide quiet operation compare to normal operation by reduces outdoor unit noise. Starting condition: When quiet button is presses. When quiet request ON time by weekly timer (Refer to control panel.) When any of above mentioned condition is achieved, this control is activated. New target FM speed = Present target FM speed - 80 rpm Minimum target FM speed = 200 rpm Cancellation condition:...
Page 52
When solar priority is NOT SET Operation condition: Solar pump operates if all of the following conditions are fulfilled: Power On. (regardless operation ON or OFF). There is operation request from solar pump station. Tank hot water temp is below solar on upper limit temp 80°C. Heat pump thermo OFF in tank mode OR Heat pump operate to room side (during operation ON and tank mode selected).
12.15 External Room Thermostat Control (Optional) Purpose: Better room temperature control to fulfill different temperature request by external room thermostat. Recommended external room thermostat: Maker Characteristic Siemen (REV200) Touch panel Siemen (RAA20) Analog Connection external room thermostat: Wire Connection and thermo characteristic of Siemen REV200: Setting L/L1 (H) Heat Thermo...
13. Protection Control 13.1 Protection Control for All Operations 13.1.1 Time Delay Safety Control The compressor will not start for three minutes after stop of operation. 13.1.2 30 Seconds Forced Operation Once the compressor starts operation, it will not stop its operation for 30 seconds. However, it can be stopped using control panel at indoor unit.
13.1.6 Low Pressure Protection Control Purpose: To protect the system operation. Detection period: After compressor on for 5 minutes. Detection conditions: When detection of Tem above 30°C. Calculation of average evaporation temperature (Tem). Use outdoor low pressure sensor. Tem use the value calculated for discharge temperature setting value After detection: Compressor stops restart again after 3 mins.
13.1.10 Crank Case Heater Control Purpose: - For compressor protection during low outdoor ambient operation (during heating low temperature operation). Control content: a. Trigger heater START condition When the outdoor air temperature is 13°C or below, and discharge temperature is 13.2°C or below. b.
14. Servicing Mode 14.1 How to Take Out Front Plate Please follow the steps below for take out front plate. Before removing the front plate of indoor unit, always switch off all power supply (i.e. indoor unit power supply, heater power supply and tank unit power supply). Remove the 2 mounting screws which located at bottom of the front plate and 1 mounting screw at the front of the plate.
14.5 How to Adjust Water Flow Rate Before adjust the water flow rate, make sure that the total water volume in the installation is 50 litres minimum. The water flow rate can be adjusted with select the water pump speed on the water pump. The default setting is moderate speed (II).
15. Maintenance Guide In order to ensure optimal performance of the unit, checks and inspections on the unit and the field wiring must be carried out regularly. Before carried out any maintenance or repair work, and removing the front plate of heat exchanger unit, always switch off all power supply (i.e.
Page 61
Reset overload protector Overload protector serves the safety purpose to prevent the water over heating. When the overload protector trip at high water temperature, take below steps to reset it. a. Take out OLP cover. b. Use a test pen to push the centre button gently in order to reset the Overload protector. c.
16. Troubleshooting Guide 16.1 Refrigeration Cycle System In order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle. Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a fan.
16.2 Relationship between the Condition of the Air-to-Water Heatpump Indoor and Outdoor Units and Pressure and Electric Current Heating Mode Condition of the Air-to-Water Heatpump indoor and outdoor Low Pressure High Pressure Electric current during operation units Water leakage or insufficient water flow rate in the system Excessive amount of refrigerant Inefficient compression...
16.3 Breakdown Self Diagnosis Function 16.3.1 Self Diagnosis Function (Three Digits Alphanumeric Code) When abnormality occur during operation, the system will stop operation, and OFF/ON control panel LED will blink and error code will display on the control panel timer display LCD. Even error code is reset by turning OFF power supply or by pressing ERROR RESET button, if the system abnormality is still un-repaired, system will again stop operation, and OFF/ON control panel LED will again blink.
16.4 Error Codes Table Diagnosis display Abnormality/Protection control Abnormality judgement Primary location to verify No abnormality detected — — Indoor/Outdoor capacity unmatched continue for 90 sec. Indoor/outdoor connection wire Indoor/outdoor PCB Specification and combination table in catalogue Outdoor compressor temperature sensor Continue for 90 sec.
Page 66
Diagnosis display Abnormality/Protection control Abnormality judgement Primary location to verify Outdoor defrost sensor abnormality Continue for 5 sec. Outdoor defrost sensor (defective or disconnected) Indoor water outlet temperature sensor Continue for 5 sec. Water outlet temperature sensor abnormality (defective or disconnected) Outdoor Current Transformer open —...
16.5 Self-diagnosis Method 16.5.1 Connection Capability Rank Abnormality (H12) Malfunction Decision Conditions: During startup operation of heating, the capability rank of indoor checked by the outdoor is used to determine connection capability rank abnormality. Malfunction Caused: Wrong model interconnected. Wrong indoor unit or outdoor unit PCB (main) used. Faulty indoor unit or outdoor unit PCB (main).
Page 68
16.5.2 Compressor Tank Temperature Sensor Abnormality (H15) Malfunction Decision Conditions: During startup and operation of heating, the temperatures detected by the compressor tank temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue for 5 seconds.
Page 69
16.5.3 Indoor Refrigerant Liquid Temperature Sensor Abnormality (H23) Malfunction Decision Conditions: During startup and operation of heating, the temperatures detected by the indoor refrigerant liquid temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty indoor unit PCB (main).
16.5.4 Compressor Low Pressure Protection (H42) Malfunction Decision Conditions: During operation of heating and after 5 minutes compressor ON, when outdoor pipe temperature below -29°C or above 26°C is detected by the outdoor pipe temperature sensor. Malfunction Caused: Dust accumulation on the outdoor unit heat exchanger. Air short circuit at outdoor unit.
Page 71
16.5.5 Water Flow Switch Abnormality (H62) Malfunction Decision Conditions: During operation of heating, the water flow detected by the indoor water flow switch is used to determine water flow error. Malfunction Caused: Air trapped in water system. Faulty water pump. Water leak in system.
Page 72
16.5.6 Outdoor Low Pressure Abnormality (H63) Malfunction Decision Conditions: During operation of heating, when the outdoor low pressure sensor output signal is 0Vdc or 5Vdc. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue 4 times in 20 minutes.
Page 73
16.5.7 Outdoor High Pressure Abnormality (H64) Malfunction Decision Conditions: During operation of heating, when the outdoor high pressure sensor output signal is 0Vdc or 5Vdc. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue 4 times in 20 minutes.
Page 74
16.5.8 Indoor Backup Heater OLP Abnormality (H70) Malfunction Decision Conditions: During operation of indoor backup heater, when no power supplies to indoor backup heater or OLP open circuit. Malfunction Caused: Faulty power supply connector connection. Faulty connector connection. Faulty indoor backup heater overload protector (OLP). Faulty indoor unit PCB (main).
Page 75
16.5.9 Tank Temperature Sensor Abnormality (H72) Malfunction Decision Conditions: When tank connection is set to ON, the temperatures detected by the tank temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty indoor unit PCB (main). Abnormality Judgment: Continue for 5 seconds.
Page 76
16.5.10 Indoor-Control Panel Communication Abnormality (H76) Malfunction Decision Conditions: During standby and operation of heating, indoor-remote control error occur. Malfunction Caused: Faulty connector connection. Faulty remote control. Faulty indoor unit PCB (main).
Page 77
16.5.11 Indoor/Outdoor Abnormal Communication (H90) Malfunction Decision Conditions: During operation of heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal. Malfunction Caused: Faulty outdoor unit PCB (main). Faulty indoor unit PCB (main). Indoor-outdoor signal transmission error due to wrong wiring.
Page 78
16.5.12 Tank Booster Heater OLP Abnormality (H91) Malfunction Decision Conditions: During operation of tank booster heater, and tank booster heater OLP open circuit. Malfunction Caused: Faulty connector connection. Faulty tank booster heater overload protector (OLP). Faulty indoor unit PCB (main). Abnormality Judgment: Continue for 60 seconds.
Page 79
16.5.13 Unspecified Voltage between Indoor and Outdoor (H95) Malfunction Decision Conditions: The supply power is detected for its requirement by the indoor/outdoor transmission. Malfunction Caused: Insufficient power supply. Faulty outdoor unit PCB (noise filter/main).
Page 80
16.5.14 Outdoor High Pressure Protection (H98) Malfunction Decision Conditions: During operation of heating, when pressure 4.0 MPa and above is detected by outdoor high pressure sensor. Malfunction Caused: Faulty water pump. Insufficient water flow rate in system. Water leak in system. 3 way closed.
Page 81
16.5.15 Indoor Freeze-up Protection (H99) Malfunction Decision Conditions: During anti-freezing control in cooling operation, when the indoor refrigerant liquid temperature < 0°C. Malfunction Caused: Faulty water pump. Insufficient water flow rate in system. Water leak in system. 2 way valve partially closed. Clogged expansion valve or strainer.
Page 82
16.5.16 Outdoor High Pressure Switch Activate (F12) Malfunction Decision Conditions: During operation of heating, when pressure 4.5MPa and above is detected by outdoor high pressure switch. Malfunction Caused: Faulty water pump. Insufficient water flow rate in system. Water leak in system. 3 way valve closed.
Page 83
16.5.17 Compressor Rotation Failure (F14) Malfunction Decision Conditions: A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit. Malfunction Caused: Compressor terminal disconnect. Faulty outdoor unit PCB (main). Faulty compressor. Abnormality Judgment: Continue 4 times in 20 minutes.
Page 84
16.5.18 Outdoor Fan Motor (DC Motor) Mechanism Locked (F15) Malfunction Decision Conditions: The rotation speed detected by the Hall IC of the fan motor during fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550rpm or < 50rpm). Malfunction Caused: Operation stop due to short circuit inside the fan motor winding.
Page 85
16.5.19 Input Over Current Detection (F16) Malfunction Decision Conditions: During operation of heating, when outdoor current above 27.9A is detected by the current transformer (CT) in the outdoor unit PCB. Malfunction Caused: Excessive refrigerant. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue 3 times in 20 minutes.
Page 86
16.5.20 Compressor Overheating (F20) Malfunction Decision Conditions: During operation of heating, when temperature above 112°C is detected by the compressor tank temperature sensor. Malfunction Caused: Faulty compressor tank temperature sensor. 3 way valve closed. Refrigerant shortage (refrigerant leakage). Clogged expansion valve or strainer. Faulty outdoor unit PCB (main).
Page 87
16.5.21 IPM Overheating (F22) Malfunction Decision Conditions: During operation of heating, when temperature 95°C is detected by the outdoor IPM temperature sensor. Malfunction Caused: Faulty outdoor unit fan motor. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue 3 times in 30 minutes.
Page 88
16.5.22 Output Over Current Detection (F23) Malfunction Decision Conditions: During operation of heating, when outdoor DC current is above 40.1 ± 5.0A (for: 6kW~9kW) OR 44.7 ± 5.0A (for: 12kW~16kW) is detected by the IPM DC Peak sensing circuitry in the outdoor unit PCB (main). Malfunction Caused: Faulty outdoor unit PCB (main).
Page 89
16.5.23 Refrigeration Cycle Abnormality (F24) Malfunction Decision Conditions: During operation of heating, compressor frequency > Frated. During operation of heating, running current: 0.65A < I < 1.65A. During operation of heating, indoor refrigerant liquid temperature - water inlet temperature < 5°C. Malfunction Caused: Faulty water inlet or indoor refrigerant liquid temperature sensors.
Page 90
16.5.24 Four Way Valve Abnormality (F25) Malfunction Decision Conditions: During heating operation, when the indoor pipe temperature of thermostat ON indoor unit < 0°C. Malfunction Caused: Faulty sensor. Faulty connector connection. Faulty outdoor unit PCB (noise filter/main). Faulty four way valve. Abnormality Judgment: Continue 4 times in 30 minutes.
Page 91
16.5.25 Outdoor High Pressure Switch Abnormal (F27) Malfunction Decision Conditions: During compressor stop, and outdoor high pressure switch is remain opened. Malfunction Caused: Faulty connector connection. Faulty switch. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue for 1 minute.
Page 92
16.5.26 Outdoor Air Temperature Sensor Abnormality (F36) Malfunction Decision Conditions: During startup and operation of heating, the temperatures detected by the outdoor air temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue for 5 seconds.
Page 93
16.5.27 Indoor Water Inlet Temperature Sensor Abnormality (F37) Malfunction Decision Conditions: During startup and operation of heating, the temperatures detected by the indoor water inlet temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty indoor unit PCB (main).
Page 94
16.5.28 Outdoor Discharge Pipe Temperature Sensor Abnormality (F40) Malfunction Decision Conditions: During startup and operation of heating, the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main).
Page 95
16.5.29 Power Factor Correction (PFC) Abnormality (F41) Malfunction Decision Conditions: During operation of heating, when the PFC protection circuitry in the outdoor unit PCB (main) senses abnormal high DC voltage level. Malfunction Caused: Power supply surge. Compressor windings not uniform. Faulty outdoor unit PCB (main).
Page 96
16.5.30 Outdoor Pipe Temperature Sensor Abnormality (F42) Malfunction Decision Conditions: During startup and operation of heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue for 5 seconds.
Page 97
16.5.31 Outdoor Defrost Temperature Sensor Abnormality (F43) Malfunction Decision Conditions: During startup and operation of heating, the temperatures detected by the outdoor defrost temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue for 5 seconds.
Page 98
16.5.32 Indoor Water Outlet Temperature Sensor Abnormality (F45) Malfunction Decision Conditions: During startup and operation of heating, the temperatures detected by the indoor water outlet temperature sensor are used to determine sensor errors. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty indoor unit PCB (main).
Page 99
16.5.33 Outdoor Current Transformer Open Circuit (F46) Malfunction Decision Conditions: A current transformer (CT) open circuit is detected by checking the compressor running frequency (≥ rated frequency) and CT detected input current (< 0.65A) for continuously 20 seconds. Malfunction Caused: CT defective.
Page 100
16.5.34 Cooling High Pressure Overload Protection (F95) Malfunction Decision Conditions: During operation of cooling, when pressure 4.0MPa and above is detected by outdoor high pressure sensor. Malfunction Caused: Dust accumulation in the outdoor unit heat exchanger. Air short circuit at outdoor unit. 2 way valve closed.
17. Disassembly and Assembly Instructions WARNING High Voltage are generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 17.1 To Remove Front Plate Please follow the steps below for take out front plate.
17.7 To Remove Air Purge Valve, Pressure Relief Valve, Flow Switch, Water Pump and Bottle Complete When reinstall the water pipe, use grease or water at the joining.
Page 105
When reinstall the water pipe, use grease or water at the joining. When reinstall the water pipe, use grease or water at the joining.
19. Exploded View and Replacement Parts List 19.1 WH-SHF09D3E5 WH-SHF12D6E5 Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 109
< Model: WH-SHF09D3E5 WH-SHF12D6E5> REF. NO. DESCRIPTION & NAME QTY. WH-SHF09D3E5 WH-SHF12D6E5 REMARKS BASE PAN CWD521266 ← HOT WATER COIL-COMPLETE CWB90C1035 ← RECEIVER CWB141039 ← FLOAT (FLOW SWITCH) CWB601008 ← TUBE CONNECTOR-COMPLETE CWT29C1043 ← FLARE NUT (5/8) CWT251061 ← FLARE NUT (7/8) CWT251064 ←...
Page 112
Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 113
< Model: WH-UH09DE5 WH-UH12DE5> REF. NO. DESCRIPTION & NAME QTY. WH-UH09DE5 WH-UH12DE5 REMARKS BASE PAN ASS’Y CWD52K1275 ← COMPRESSOR 4JD650XAA22 ← BUSHING - COMPRESSOR MOUNT CWH50055 ← NUT-COMPRESSOR MOUNT CWH561049 ← PACKING CWB811017 ← CRANKCASE HEATER CWA341053 ← CONDENSER COMPLETE CWB32C3494 ←...
Page 114
REF. NO. DESCRIPTION & NAME QTY. WH-UH09DE5 WH-UH12DE5 REMARKS MAGNET RELAYS K6C1AYY00003 ← V-COIL COMPLETE - EXP. VALVE (BYPASS) CWA43C2335 ← SENSOR-COMP. TEMP COIL (BYPASS) CWA50C2797 ← ACCESSORY CO.(DRAIN ELBOW) CWG87C2030 ← Note: All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). “O”...