Step 2 - Installation Of The Outdoor Unit; Step 3 - Refrigerant Line Connections - Haier 2U18MS2VHB Installation Manual

Ductless split heat pump
Hide thumbs Also See for 2U18MS2VHB:
Table of Contents

Advertisement

Set the Outdoor Unit
Step - 2.1
2.1
Set the unit on mount or pad. If located in snow area, use heat
pump risers to elevate the outdoor unit.
Make sure the outdoor unit is installed level and is stable.
Attaching Drain Elbow to Outdoor Unit
Step - 2.2
2.2
If the unit is located in an area where freezing can occur, do
not install the rubber drain fitting onto the bottom of the unit.
If the area stays above freezing. Insert the drain fitting per
these instructions.
If attaching the supplied drain elbow to the outdoor unit,
do so prior to attaching the refrigerant lines and wiring.
Extension piping to attach to this fitting is field supplied.
Use drain plug for drainage.
If the drain port is covered by a mounting base or floor
surface, place additional foot bases of at least 1 1/6 in. in
height under the outdoor unit's feet.
In cold areas, do not use a drain hose with the outdoor
unit. (Otherwise, drain water may freeze, impairing heating
performance.)
Piping Limits
The maximum lift allowed between the outdoor unit and
COMBINED indoor units is 50 feet total of all installed units.
For example, 3 units with 15 elevation each is 45 feet.
The maximum allowable piping length for ALL INSTALLED
indoor units is a total of:
18K Outdoor Models: 100 Feet
24K Outdoor Models: 200 Feet
36K Outdoor Models: 230 Feet
The maximum refrigerant piping length allowable to a
Cassette unit is 82 feet.
PAGE 6

Step 2 - Installation of the Outdoor Unit

Step 3 - Refrigerant Line Connections

INSTALLATION
Step 2.2
Pipe Size
Use the refrigerant line size that is indicated in the
specification information for each indoor unit. Use stub
adapters to adapt size to the outdoor unit if necessary.

Advertisement

Table of Contents
loading

Table of Contents