If the coating on the fastening area is stripped off, the nuts rust easily.
Dimensions (bottom view) (unit of measurement: mm)
174
84
259

(4)Drain work of the outdoor unit

In case drain work on your outdoor unit is neccessary, follow the guidelines below.
•Two drain outlets are provided in the bottom plate of unit (drain plug and drain hose are field supply).
• In cold areas, do not use a drain hose with the unit. Otherwise,drain water may freeze and block the drain. In case
the use of a drain hose is unavoidable for one reason or another, it is recommended to install a heater tape in order
to protect drain from freezing.
•Make sure the drain works properly.
NOTICE
If drain holes of the outdoor unit are covered by a mounting base or by floor surface, raise the unit in order to
provide a free space of more than 100 mm under the outdoor unit.

(5)Requirements and recommendations for the hydraulic circuit

Expansion
A 600
C
439
D
E
Pressure gage
Expansion
tank
"Y" type Filter
Pressure
gage
Auto
water
supply
valve
Solar or
Boiler
Boiler
Pressure
gage
tank
"Y" type Filter
Pressure
gage
Auto
water
supply
valve
174
80
F
70
3-WayValve
Pump
tank
Water tank
Senser
Booster heater
Pump
3-Way
tank
Valve
47
A leg pitch1
B leg pitch2
C Front grill (air outlet side)
D Drain hole
E Bottom frame
F Knock-out hole (for piping line)
Air Purger
Fan coil
Floor heating
Air Purger
Fan coil
Floor heating