Option 13 - Optimum Start Control/ Delayed Start
Event Setting (Option 11 set to 1 or 2)
The Optimum start or delayed start control can
be applied to event 1 only or to each event of the
day which requires a higher temperature than the
previous event. Press + until Option 13 is displayed,
use Λ or V to select required setting (only active if
Option 11 is set to 1 or 2).
0 = Applies to Event 1 only (Factory Setting)
1 = Applies to all Events and will activate on those
events which require a higher temperature compared
to the previous event.
3.1 Overview of installer selectable features which
may aff ect the operation of your thermostat

3.1.1 Temperature range limitation

This allows the installer to programme both upper and lower
temperature limits. It may limit the upper and lower temperature
that you are able to set on the thermostat.

3.1.2 Temperature override limitation

This allows the installer to limit the number of degrees that you can
override the programmed temperature by, it also allows the installer
to set rules regarding how long a temperature override will remain
in place.

3.1.3 Keyboard lock

This allows the installer to limit or lock the keyboard to prevent
unauthorised changes to programme values and limits overrides.
Note:
Partial keyboard - Padlock symbol will fl ash
Full keyboard - Steady Padlock symbol
Danfoss Heating
GB
27