Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as follows.
Intake Air Temperature.
Setting Temperature .+3°C
(Compressor OFF)
Setting Temperature
(Compressor ON)
INDOOR FAN
COMPRESSOR
A point; While the indoor Heat-Exchanger temperature is higher than 40°C fan operates at low speed,
when it becomes lower than 40˚C fan stops.
B point; When the indoor Heat-Exchanger temperature is higher than 42°C, fan operates at selected fan
speed, when it becomes lower than 39°C, the fan operates at low speed.
Hot-Start Control
• The indoor fan sdoes not rotate until the evaporator piping temperature reaches to 25°C.
• If the evaporator piping temperature drops below 22°C, indoor fan stops again.
• The operation diagram is as follows.
PIPING
TEMPERATURE
minimum 3min
1min
minimum
10sec.
(Hot Start)
Selected
Low
Low
OFF
Fan Speed
ON
25°C
22°C
INDOOR FAN
OFF
COMPRESSOR
A
B
minimum
1min.
OFF
Low
OFF
ON
1min
Selected
LOW
fan speed
ON
Operation Details
A
minimum
10sec.
Selecting fan
Low
OFF
speed
OFF
Service Manual 29