1.1.2 Heat Pump
Model
Cooling Capacity
Heating Capacity
Casing
Dimensions (W*H*D) Body
Coil
Rows x Columns x FPI
Face Area
Type
Motor Output
Running Current
Fan
Air Flow Rate(H/M/L)
External Static Pressure
Drive
Speed control
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Safety Device
Liquid Side
Pipe Connections Gas Side
Drain Pipe(ID)
Net Weight
Noise Level (Sound Press,1.5m, H/M/L)
Power Supply
Refrigerant Control
Power cable
Transmission cable
Stuffing Quantity Without S/parts
Notes:-
1. Capacities are based on the following conditions:
Cooling
• Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
Heating
• Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. L.E.V.: Linear Expansion Valve
LRNN076BTG(Q)0
Unit
W
2,100
1,806
kcal/h
7,165
Btu/h
W
2,363
2,031
kcal/h
Btu/h
8,061
Galvanized Steel Plate
708*230*537
mm
28*9.1*21.2
inch
2*12*18
m
2
0.12
Sirocco Fan
W
40
0.30
A
8.7/7.5/6.2
cmm
307/265/219
cfm
19.6
Pa
Direct
Phase Control
Mi c roprocessor, Thermostat for cool i n g and heati n g Mi c roprocessor, Thermostat for cool i n g and heati n g Mi c roprocessor, Thermostat for cool i n g and heati n g
Foamed polystrene
-
Fuse, Thermal Fuse for Fan Motor
Ø6.35(1/4)
mm(inch)
mm(inch)
Ø12.7(1/2)
25.4
mm
kg(lbs)
25(55.1)
35/33/31
dBA±3
1 / 220 ~ 240 / 50
Ø / V / Hz
LEV
CV2.0 X 3C
mm
2
mm
2
CVV-SB 1.25 X 2C
172/356
20/40ft
Heat Pump (50Hz)
LRNN096BTG(Q)0
LRNN126BTG(Q)0
2,600
2,235
8,871
2,925
2,515
9,980
Galvanized Steel Plate
Galvanized Steel Plate
708*230*537
28*9.1*21.2
2*12*18
0.12
Sirocco Fan
40
0.30
9.5/ 8.7 / 7.5
336/307/265
19.6
Direct
Phase Control
Foamed polystrene
Foamed polystrene
-
Fuse, Thermal Fuse for Fan Motor
Fuse, Thermal Fuse for Fan Motor
Ø6.35(1/4)
Ø12.7(1/2)
25.4
25(55.1)
36/34/32
1 / 220 ~ 240 / 50
LEV
CV2.0 X 3C
CVV-SB 1.25 X 2C
CVV-SB 1.25 X 2C
172/356
Service Manual 77
Specifications
3,500
3,009
11,942
3,938
3,385
13,435
708*230*537
28*9.1*21.2
2*12*18
0.12
Sirocco Fan
40
0.30
10.6/ 9.5 / 8.7
375/336/307
19.6
Direct
Phase Control
-
Ø6.35(1/4)
Ø12.7(1/2)
25.4
25(55.1)
37/35/33
1 / 220 ~ 240 / 50
LEV
CV2.0 X 3C
172/356
Conversion Formula
Kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m
3
/min x 35.3

Hide quick links: