2.1.3 Compressor stage during oil return control

Compressor stage at normal oil return state
2 unit combination : 60Hz + stage 2
3 unit combination : 60Hz + stage 3
4 unit combination : 60Hz + stage 4
High pressure limit
Pressure range
2441 kPa
~ 2657 kPa
< 2441 kPa
Low pressure limit
Pressure range
> 101 kPa
36kPa ~ 52kPa
* Low pressure limit under –10˚C= normal limit pressure – 26kPa
2.1.3 Compressor stage during oil return control
Compressor stage at normal oil return state
Component
Inv Compressor
Sub unit 's
compressor
Fan
Main LEV
4 way valve
Subcooling LEV
Hot gas bypass
valve
Compressor stage
Emergncy Control
Normal oil return
Compressor stage
Normal oil return
Emergncy Control
Starting
30 Hz
All off
High pressure
0 Hz
Full open
On
off
min.
On
Running
60 Hz
On
High pressure
control
Full open
Base pulse
Off
min.
On
Function
Ending
30 Hz
Off
control
On
min.
On