3. Route the flexible vent.
4. Install firestop/spacers at ceiling and wall penetrations.
5. Attach the flexible vent to the termination.

Complete the Field Wiring

11.
The ground supply lead must be connected to the wire attached to the green ground screw
located on the outlet box (see wiring diagrams). Failure to do so will result in a potential
safety hazard. The appliance must be electrically grounded in accordance with local codes
or, in the absence of local codes, the National Electrical Code, ANSI/NFPA 70—latest
edition (in Canada, the current CSA C22-1 Canadian Electrical Code).
Label all wires prior to disconnection when servicing controls. Wiring errors can cause
improper and dangerous operation.
Au moment de l'entretien des commandes, étiquetez tous les fils avant de les débrancher.
Des erreurs de cáblage peuvent entraîner un fonctionnement inadéquat et dangereux.
Verify proper operation after servicing.
The gas valve is set in place and pre-wired at the factory for both millivolt and electronic models.
Millivolt Wiring
Millivolt units are not provided with factory-installed controls; therefore, one of the optional control switches is
required to operate the unit (Page 64):
See the Operation section on Page 50 for more details.
36
1. If installing an ON/OFF wall switch or thermostat, mount it in a convenient location on a wall near the fireplace.
d. Slide the outer flexible vent over the adaptor collar. Ensure the flexible vent completely engages the adaptor collar
1 3/4" from the end, and that it is free from damage or tears.
e. Slide the gear clamp down and tighten it fully to secure the flexible vent to the adaptor outer collar
approximately 3/4" from the end of the flexible vent.
f. Install three (3) screws 120° apart through the flexible vent and into the adaptor collar just below the gear
clamp to provide additional security to the connection.
NOTE: Ensure that the flexible vent is properly routed to provide the required clearance. Do NOT allow the flexible vent
to bend in a radius tighter than 5" (127 mm) (Figure 30). Place the internal flexible vent spacers evenly and avoid
kinking the inner vent. Support horizontal sections of flexible vent with metal straps at 2 ft (0.61 m) intervals.
SF4.5 VF firestop/spacer for ceilings
SF4.5 HF firestop/spacer for walls
NOTE: See the appropriate sections and figures shown throughout the venting section for installation
requirements.
NOTE: Secure Flex
components can be purchased separately and attached to bulk lengths of Secure Flex flexible
®
vent cut to size at the job site. Attach the flexible vent to the Secure Flex terminations as it was attached to the
adaptor (Figure 29).
NOTE: Attach Secure Flex vent to Secure Flex terminations only. Do NOT substitute Secure Vent
or Secure Vent adaptor for Secure Flex components. Secure Flex termination and adaptor collars are a
different circumference than Secure Vent collars. Secure Flex vent has an longer center tube to improve
ease-of-installation.
S'assurer que l'appareil fonctionne adéquatement une fois l'entretien terminé.
ON/OFF Wall Switch,
Unit-Mountable ON/OFF Switch *,
Thermostat, or
Remote Control.
CAUTION
CAUTION
ATTENTION
Installation
900285-00 11/2014
terminations
®

Advertisement

Table of Contents
loading

This manual is also suitable for:

Drt3035Drt3045Drt3040

Table of Contents