Refrigerant Connections - Lennox WING Application Manual

Lennox air conditioner application guide wing
Table of Contents

Advertisement

REFRIGERANT CONNECTIONS

REFRIGERANT CHARGE
MODEL
COOLING
ONLY
HEAT
PUMP
MODEL
COOLING
ONLY
HEAT
PUMP
(*)
Refrigerant charge R-22 precharge from factory on the outdoor unit.
(**)
Meter of installation line where outdoor unit is precharged+charge also to the group
(***) If line is different to meters indicated on table put more or less charge of refrigerant per meter indicated.
If you need to install a group WING 5CFK, with distance of line between indoor and outdoor unit of 6 meter. The
refrigerant charge R-407C needed in the installation is:
OUTDOOR UNITS TYPE KJF-K/ KJB
(gr.) (*)
(gr.) (**)
(gr.) (***)
(gr.) (*)
(gr.) (**)
(gr.) (***)
OUTDOOR UNITS TIPO KCF-K/ KCB
(gr.) (*)
(gr.) (**)
(gr.) (***)
(gr.) (*)
(gr.) (**)
(gr.) (***)
Charge precharge on outdoor unit
Charge per line
Total charge of the installation = 5355 gr
2,8
3
4
1.650
2.500
2.600
5
5
5
30
30
30
1.775
2.500
2.800
5
5
5
45
45
45
3
2,8
4
2.255
2.350
3.070
5
5
0
30
30
30
2.425
2.525
3.400
5
5
0/5
45
45
45
EXAMPLE:
=
55gr/m x (6-5)m
=
19
5
2.600
5
55
3.500
5
105
5
4.950
5
55
5.300
5/0
105
5300
55