REFRIGERANT CONNECTIONS

To locate the outdoor and the indoor units, refer to the following information :
A
Outdoor unit
Indoor unit
1
Circuit 1
2
Circuit 2
REFRIGERANT LINES SELECTION
REFRIGERANT LINES
0 to 30 m.
(Standard con-
nection of unit)
Total line length.
(Length refri-
gerant lines
between indoor
unit and outdoor
unit.)
30 to 65 m.
0 to 30 m.
(Standard con-
nection of unit)
Total line length.
(Length refri-
gerant lines
between indoor
unit and outdoor
unit.)
30 to 65 m.
Application Guide • AIRCOOLAIR-AGU-1603-E
2%
2
1
A
V
2%
C1
Ø Liquid
C2
C1
Ø Gas
C2
Max. nr of bends
C1
Ø Liquid
C2
C1
Ø Gas
C2
Max. nr of bends
C1
Ø Liquid
C2
C1
Ø Gas
C2
Max. nr of bends
C1
Ø Liquid
C2
C1
Ø Gas
C2
Max. nr of bends
B
Indoor
unit
As standard, distance between indoor and outdoor units is 40 meters.
This distance reaches 65 meters with long distance option.
V Maximum length = 16 meters
L : Maximum total length (vertical + horizontal = 65 meters)
020S
025S
030S
1/2"
5/8"
5/8"
n/a
n/a
n/a
7/8"
1 1/8"
1 1/8"
n/a
n/a
n/a
6
12
8
5/8"
5/8"
5/8"
n/a
n/a
n/a
1 1/8"
1 1/8"
1 3/8"
n/a
n/a
n/a
12
18
18
070D
085D
100D
5/8"
5/8"
3/4"
5/8"
5/8"
5/8"
1 3/8"
1 3/8"
1 5/8"
1 3/8"
1 3/8"
1 3/8"
18
12
12
3/4"
3/4"
7/8"
3/4"
3/4"
3/4"
1 3/8"
1 5/8"
1 5/8"
1 3/8"
1 5/8"
1 5/8"
18
18
12
B
2%
1
Outdoor unit
2
L
Sizes
035S
040S
045D
5/8"
5/8"
5/8"
n/a
n/a
5/8"
1 3/8"
1 3/8"
1 1/8"
n/a
n/a
1 1/8"
18
12
12
3/4"
3/4"
5/8"
n/a
n/a
5/8"
1 3/8"
1 5/8"
1 1/8"
n/a
n/a
1 1/8"
18
18
18
120D
140D
200D
3/4"
3/4"
7/8"
5/8"
3/4"
7/8"
1 5/8"
1 5/8"
1 5/8"
1 3/8"
1 5/8"
1 5/8"
12
12
12
7/8"
7/8"
n/a
3/4"
7/8"
n/a
1 5/8"
1 5/8"
n/a
1 5/8"
1 5/8"
n/a
12
12
n/a
n/a: not available
055D
5/8"
5/8"
1 1/8"
1 1/8"
8
5/8"
5/8"
1 3/8"
1 3/8"
18
230D
7/8"
7/8"
2 1/8"
2 1/8"
12
n/a
n/a
n/a
n/a
n/a