Outdoor Unit
Compressor Reverse Rotation
Protection Control
• To protect compressor from reverse
rotation when there is an instantaneous
power failure.
Overload Protector
• Inner protector.
60 Secs. Forced Operation Control
• Once the compressor is activated, it
does not stop within the first 60 secs.
However, it stops immediately with
remote control stop signal.
Outdoor Fan Operation Control
• 4-pole induction motor (2 speed).
• For Cooling or Soft Dry operation
Hi-speed ............. When outdoor
temperature reaches to 31°C.
Lo-speed ............. When outdoor
temperature reaches to 29°C.
5