Controls from the UAD:
bit0= terminal status (0= not connected; 1= available)
bit2; bit1= mode set from μAD (00= AUTO; 01= cooling;
10= heating)
bit3= enable dehumidifi cation
bit4= enable humidifi cation
bit5= terminal probe alarm
bit6= activate boiler output
bit7= 0= process mode active; 1= process mode
disabled
-
Signals to the μAD
bit0= cool/heat request from uAD in progress
bit1= cool/heat request accepted from μAD (1= cooling;
0= heating)
bit2= start fans
bit3= alarm active on μCH
bit4= RTC available on μCH2 SE
-
DTE value saved in EEPROM
-
Internal set point compensated in the event of
autotuning
-
Ambient set point (from μAD)
-
Set point variation from μAM (μedronic)
-
Diff erential for the ambient set point
-
Controls by the μAD from save
-
"Active alarm signal:
bit0= probe alarm (E1,E2,E,E4,E5,E6,E7,E8)
bit1= high pressure alarm (HP1, HP2)
bit2= low pressure alarm (LP1, LP2)
bit3= fl ow switch alarm (FL)
bit4= expansion communication alarm (ESP)
bit5= EE2PROM alarm (EPB)
bit6= antifreeze alarm (A1, A2)
bit7= thermal overload alarm (TP, TP1, TP2)
bit8= hour counter alarm (H1, H2, H, H4)"
-
Terminal humidity probe (per terminal μAD)
-
Reset alarms
-
Digital input B
4.3.13 Supervisor-only variables
display
parameter and description
indicat.
-
Indicates the unit parameter (Carel SV communication)
-
Gain constant for pressure probe calibration
-
Off set constant for pressure probe calibration
-
Compressor 1 operating hours
-
Compressor 2 operating hours
-
Compressor 3 operating hours
-
Compressor 4 operating hours
-
Compressor pump operating hours
-
Evaporator pump operating hours
-
Alarms/warnings for EVD1:
bit0= low superheat alarm
bit1= EEPROM alarm
bit2= probe alarm
bit3= MOP warning
bit4= LOP warning
bit5= high suction temperature warning
bit6= valve open after power failure alarm
bit7= fl at battery alarm
-
Controls/status indicators for EVD1:
bit0; bit1= comp. load step (0= 0%; 1= 50%; 2= 100%)
bit2= standby circuit 2 (0= ON; 1= standby)
bit3= chiller/pump circuit 2 (0= chiller; 1= pump)
bit4= defrost circuit 2 (0= no defrost; 1= defrost)
bit5= forced valve closing (for pump down)
bit6= enable smart defrost
bit7= enable low noise
bit8= type of condenser probe (0= temp/1= press)
bit9= condenser temp/press probe available
bit10= restart unit after valve open alarm (set in reset_
alarms)
bit11= enable control for driver 2
-
Communication of the logical status of the digital outputs
to expansion:
bit0= compressor
bit1= compressor 4
bit2= heater 2
bit3= reversing valve
bit4= warning
bit5= condenser pump
bit6= fans in alarm status
bit7= fan status in alarm (ON= 1; ofF= 0)
bit8= speed to be set (100%= 1; speed from probe= 0)
bit9= indicates fans 2 for defrost circuit 2
bit10= heater 1
bit11= open damper
bit12= close damper
bit13= humidifi er
μC
2
SE - +030220426 - rel. 2.1 - 09.06.2010
D
0
1023
1
D
0
255
-
D
0
0
-
D
0
0
-
D
-400 1760
0,1
D
-100 100
0,1
D
-100 100
0,1
D
0
32767
1
D
0
32767
1
D
0
1000
%
0,1
D
0
1
1
D
0
1
-
default
min. max.
U.O.M. variat.
level
F
0
250
-
F
0
16000
-
F
-8000 8000
-
D
0
8000
-
D
0
8000
-
D
0
8000
-
D
0
8000
-
D
0
8000
-
D
0
8000
-
D
0
0
-
D
0
0
-
D
0
4200
-
33
0
135 (R/W)
342
0
136 (R)
343
0
98 (R)
98
0
97 (R)
97
0
95 (R/W)
95
0
96 (R/W)
96
0
94 (R/W)
94
0
-
137 (R/W)
344
0
-
128 (R/W)
335
0
129 (R/W)
129
0
78 (R/W)
78
0
79 (R)
79
def.
visibility supervis.
Modbus variable
variable
108
(R)
207
1000
(R)
207
0
(R)
207
0
(R)
207
0
(R)
207
0
(R)
207
0
(R)
207
0
(R)
207
0
(R)
207
0
(R)
207
0
(R)
207
0
(R)
207
Integer
Integer
Analog
Analog
Analog
Analog
Analog
Integer
Integer
Analog
Digital
Digital
Table 4.m
type
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer
Integer

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents