Mitsubishi Electric PCH-2GKHA Service Manual page 31

Hide thumbs Also See for PCH-2GKHA:
Table of Contents

Advertisement

2-2 DRY operation
4
<DRY operation time chart>
Operation starts by
P O W E R b u t t o n
ON.
ON
Thermostat
OFF
ON
Indoor fan
OFF
Auto vane
close
ON
Drain pump
OFF
(OPTIONAL)
ON
Booster heater
OFF
ON
Compressor
OFF
w1 Even if the room temperature rises above the set temperature during this period, the compressor will not start until this period has ended.
(1) Compressor control
13-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2The compressor runs when the room temperature is higher than the set temperature.
The compressor stops when the room temperature is equal to or lower than the set temperature.
3The compressor stops in check mode or during protective functions.
<How to operate>
1 Press POWER ON/OFF button.
2 Press the a button to display " e ".
FILTER
3 Press the i TEMP button to set the desired temperature.
CHECK MODE
TEST RUN
Room temperature
becomes equal to
set temperature.
Low speed
Initally 35degrees (SW5-3:OFF) or 20degrees (SW5-3:ON) discharge
(Changeable by remote controller setting)
OFF
Minimum 3 minutes w1
NOTE: The set temperature changes 1°C when the
button is pressed one time.
Dry 19°C to 30°C.
Room temperature
rises above set
temperature.
Operation stops by
P O W E R b u t t o n
OFF.
LOW speed
close
3 minutes
or
31