BEFORE INSTALLATION

The installation site must be established by the system designer or other qualified professional, taking
account of the technical requisites and current standards and legislation.
PCG fan coils must be installed by an authorized company only.
PCG fan coils are designed for installation in a false ceiling, for intake of fresh air from outside and for
deviation of a small part of the treated air for discharge in a neighboring room.
They must be installed in such a way as to enable treated air to circulate throughout the room and in
respect of the minimum distances required for technical maintenance operations.
1. It is advisable to place the unit close to the installation site without removing it from the packaging.
2.
Do not put heavy tools or weights on the packaging.
3.
Upon receipt, the unit and the packaging must be checked for damage sustained in transit and if
necessary, a damage claim must be filed with the shipping company.
4.
Check immediately for installation accessories inside the packaging.
5.
Do not lift unit by the condensate drain discharge pipe or by the water connections; lift it by the
four corners.(Fig.1)
6.
Check and note the unit serial number.
Fig.1
SELECT LOCATION
1.
Do not install the unit in rooms where flammable gas or alkaline acid substances are present.
Aluminum/copper coils and/or internal plastic components can be damaged irreparably.
2.
Do not install in workshops or kitchens; oil vapors drawn in by treated air might deposit on the
coils and alter their performance or damage the internal plastic parts of the unit.
3.
Installation of the unit will be facilitated by using a stacker and inserting a plywood sheet between
the unit and the elevated stacker.(Fig.2)
4.
It is recommended to position the unit as centrally as possible in the room to ensure optimum air
distribution. (Fig.3)
Generally the best louver position is the one which allows air diffusion along the ceiling.
Alternatively intermediate positions can be selected.
5.
Check that it is possible to remove panels from ceiling in the selected position, to allow enough
clearance for maintenance and servicing operations.
Fig.3
HYDRONIC CASSETTE
Fig.2
15