4.6 Fuel treatment system control cabinet – Control elements
No.
Color
1
Green
2
Red
3
Yellow
4
Red
5
Yellow
6
Red
7
8
White
9
10
Caption
Meaning/Function
Signal lamp
Indicates „Pump running"
Signal lamp
Indicates „Pump fault"
Illuminated but-
Indicates „Water drain" / Press to drain water manually.
ton
Illuminated but-
Indicates „Water alarm" / Press to acknowledge.
ton
Signal lamp
Indicates „Filter warning" due to increased differential pressure.
Illuminated but-
Indicates „Replace filter element" / Press to acknowledge.
ton
Switch
Pump operating mode "Remote– 0 – Manual"
Switch position "Remote": Pump is controlled at LOP
Switch position "0": Pump is switched OFF
Switch position "Manual": Pump is started manually
Signal lamp
Indicates „Control voltage present".
Hour meter
Indicates runtime of pump.
Master switch
MS150047/04E 2013-07 | Operation | 75