Mitsubishi Electric PKFY-P15VBM-E Technical & Service Manual page 3

Series pkfy wall mounted r410a/r407c/r22 split-type, heat pump air conditioners
Hide thumbs Also See for PKFY-P15VBM-E:
Table of Contents

Advertisement

[2] Refrigerant recharging
(1) Refrigerant recharging process
1 Direct charging from the cylinder.
·R407C cylinder available on the market has a syphon pipe.
·Leave the syphon pipe cylinder standing and recharge it.
(By liquid refrigerant)
Gravimeter
(2) Recharge in refrigerant leakage case
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release the refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.
[3] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
No.
Tool name
Gauge manifold
Charge hose
Electronic scale
Gas leak detector
Adapter for reverse flow check
Refrigerant charge base
Refrigerant cylinder
Refrigerant recovery equipment
Unit
Specifications
·Only for R407C
·Use the existing fitting SPECIFICATIONS. (UNF7/16)
·Use high-tension side pressure of 3.43MPa·G or over.
·Only for R407C
·Use pressure performance of 5.10MPa·G or over.
·Use the detector for R134a or R407C.
·Attach to vacuum pump.
·For R407C
·Top of cylinder (Brown)
·Cylinder with syphon
3 3