Mitsubishi Electric PKFY-P15VBM-E Technical & Service Manual page 20

Series pkfy wall mounted r410a/r407c/r22 split-type, heat pump air conditioners
Hide thumbs Also See for PKFY-P15VBM-E:
Table of Contents

Advertisement

8-3-2. Indoor power board
PKFY-P15VBM-E
PKFY-P20VBM-E(R1)
PKFY-P25VBM-E(R1)
CN2M
Connected to the terminal block (TB5)
(M-NET transmission connecting wire)
24-30V DC (non-polar)
CN35P
Connected to the indoor controller board
(CN35M)
CN53P
Connected to the indoor controller board
(CN53M)
Between 1 to 2 24-30V DC (non-polat)
Between 3 to 5 12.5-13.7V DC (Pin3 (+))
Between 4 to 5 11.5-12.7V DC (Pin4 (+))
LED1
Main power supply
(Indoor unit : 220-240V)
8-3-3. Address board
PKFY-P15VBM-E
PKFY-P20VBM-E(R1)
PKFY-P25VBM-E(R1)
SW1
Function setting
SW12
SW11
Address setting
Address setting
10ths digit
1s digit
FAN
Fan motor output (MF)
20
CND
Power supply for
indoor controller board
Between 1 to 3 220-240V AC
FUSE
6.3A 250V