1.1 DESCRIPTION OF THE FIRE CONTROL PANEL FASCIA (continued...)
11
FIRE BRIGADE ACKNOWLEDGED: If the LED is AMBER it indicates that the transmission has been acknowledged.
12
ALARM SILENCE
: Pressing this button will silence all alarm sounders and buzzers during a FIRE condition as well as
all buzzers during a FAULT condition.
13
ALARM SILENCE
: If the LED is AMBER it indicates that a FIRE condition has been silenced.
14
SYSTEM RESET
: Pressing this button restores the panel to its normal operating condition after an alarm. Alarms must
be silenced before a SYSTEM RESET can be performed. A SYSTEM RESET does not clear any settings or disablements;
it only clears FIRE and FAULT conditions (and then only if the source of the FIRE or FAULT has been cleared).
15
LAMP TEST
: Whilst this button is depressed all of the panel's LEDs will be illuminated and all of the LCD display pixels
will be set to black. Use this button to confirm the LEDs and LCD display are functional.
16
SOUND ALARMS
: Pressing this button will activate all sounders and panel buzzers (main panel and Repeaters).
Pressing the button again or pressing ALARM SILENCE (
17
SOUND ALARMS
: If the LED is RED it means that the SOUND ALARMS function has been activated.
18
ACTIVE DELAYS
: Delays can be configured for the sounders, I/O modules and fire brigade transmission using the
programming functions. Pressing this button enables or disables these delays.
19
ACTIVE DELAYS
: If the LED is AMBER it means that the delays are active.
20
SELECTED DETECTORS
DISABLEMENT. When this button is activated those detectors will be disabled (isolated). Note that this button will only
operate if at least one detector has been set for SELECTIVE DISABLEMENT.
21
SELECTED DETECTORS
22
FIRE BRIGADE TRANSMISSION
23
FIRE BRIGADE TRANSMISSION
24
AUXILIARY RELAYS
: Pressing this switch disables or enables all the relay and I/O module outputs.
25
AUXILIARY RELAYS
: If the LED is AMBER it means that the relay and I/O module outputs are disabled.
26
DISABLED
: If there are disablements then pressing this button will show the disablements on the LCD display. If there
are more disablements than can be shown on the LCD display at one time then subsequent presses of this button will
step through all the disablements.
27
DISABLED
: If the LED is AMBER it means that there is at least one disablement.
28
TEST
: If there are ZONES in test mode then pressing this button will show those ZONES on the LCD display. If more
ZONES are in test mode than can be shown on the LCD display at one time then subsequent presses of the button will
step through all the ZONES in test mode.
TEST
: If the LED is AMBER it means that one or more ZONES are in test mode.
29
30
FAULT
: If there is more than one FAULT, or if there is at least one FAULT and a FIRE, pressing this button will display
the next FAULT report on the LCD display for 20 seconds. Subsequent presses will step through all the FAULT reports.
31
FAULT
: If the LED is flashing AMBER it means that are FAULT reports to be reviewed. If the LED is steady AMBER then
all FAULT reports have been reviewed.
32
FIRE
: If there is more than one FIRE pressing this button will display the next FIRE report on the LCD display for 20
seconds. Subsequent presses will step through all the FIRE reports.
33
FIRE
: If the LED is flashing RED it means that there are FIRE reports to be reviewed. If the LED is steady RED then all
FIRE reports have been reviewed.
34
PAPER FEED
: Pressing this switch will advance paper through the printer.
35
INFRA-RED SENSOR
: When using the Remote Infra-Red Keypad it is important that the remote is pointed towards
this sensor.
OPERATION & MAINTENANCE MANUAL
REVISION 0.7a
16-04-2004
OPERATION
: Using the programming functions individual detectors can be set for SELECTIVE
: If the LED is AMBER it means that the selected detectors are isolated.
: Pressing this button disables or enables the fire brigade transmission.
: If the LED is AMBER it means that the transmission is disabled.
12
) will silence the sounders and buzzers.