Global JUNO-NET Operation & Maintenance Manual page 21

Fire alarm control panel
Table of Contents

Advertisement

JUNO-NET
MAINTENANCE
1-5 Read/Clear Autostart Count
Every time the Main Panel has a Master Reset or it's power is cycled the Autostart count is incremented.
SYSTEM RESETs from the front panel button do not increment the Autostart count.
7-1 Device Count, Type & Value
Use this function to check that all Sub-panels are present and that all devices are present.
Use +/- to select the Analogue Loop number and 0-9 and
to select the device address on that
loop.
This function is also useful to confirm the address of the various different types of devices connected to the
Analogue Loops.
Note that in Installation Mode all information is live i.e. the count of devices will change as the panel
learns and device types will be updated if they change. In Active Mode only the device value is live.
7-2 Test Sounders
Use this function to test the audibility of the sounders in a more comfortable manner than pressing
SOUND ALARMS.
Main Panel
The Main Panel Conventional Sounders will sound for 1 second then be silenced for 9 seconds.
Standard Sub-panels
Conventional Sounders and Loop Sounders are operated for 1 second then silenced for 9 seconds.
Integrated Sub-panels
Conventional Sounders and Loop Sounders are operated for 1 second then silenced for 9 seconds.
Conventional Sounder operation for a Repeater Integrated Sub-panel will be synchronized to the Loop
Sounder operation.
20
OPERATION & MAINTENANCE MANUAL
REVISION 0.7a
16-04-2004