MAINTENANCE
7-3 Sounders on Test Activation
This function allows you to choose an audible confirmation that a device has detected a fire. The audible
confirmation consists of a 1 second period of sounder operation. The settings selected by this function are
used by '7-4 Test Zones' and '6-4-1 Activate ASET Mode (SAM)'.
ALL SOUNDERS ON DETECTOR TEST activates the Main Panel Conventional Sounders and all
Conventional Sounders and Loop Sounders on the Sub-panel under test.
SUB_PANEL SOUNDERS ON DETECTOR TEST only operates the Conventional Sounders and Loop
Sounders on the Sub-panel under test. I.e. The Sub-panel that the detector under test is physically
connected to.
Note -
using this function AFTER '7-4 Test Zones' and '6-4-1 Activate ASET Mode (SAM)' will NOT
change the settings for the zones already in test mode and the loops already in ASET mode.
7-4 Test Zones
Select the Zones you wish to put into test mode.
Exit programming mode, but DO NOT press SYSTEM RESET as this clears all test modes.
In test mode when a detector is activated the LED on the detector will be illuminated and the event will be
reported on the Main Panel (and Repeaters) for 15 seconds. If selected then the sounders will also operate
for 1 second. The LED on the detector is not latched and will clear when the alarm level falls below the
alarm threshold for the device.
Pressing TEST QUEUE REVIEW will report the zones that are in Test Mode.
7-5 Sub-Panel LED Test
This function is used to confirm that all the Standard Sub-panel LEDs are functional.
Each of the LEDs on all sub-panels will operate in sequence.
The test is only performed whilst LED TEST MODE is shown within this programming function.
There is no need to press ENTER just use UP/DOWN to toggle between LED NORMAL MODE and LED
TEST MODE.
This test has no effect on Integrated Sub-panels.
Upon exit of this programming function normal functionality is automatically restored.