Troubleshooting Check Table - Mitsubishi Electric MUZ-FH09NA Service Manual

Mitsubishi electric split-type air conditioners outdoor unit service manual
Hide thumbs Also See for MUZ-FH09NA:
Table of Contents

Advertisement

10-3. TROUBLESHOOTING CHECK TABLE

No.
Symptom
LED indication
Outdoor unit
1-time fl ash every
does not op-
2.5 seconds
erate.
1
2
3
6-time fl ash
2.5 seconds OFF
4
11-time fl ash
5
2.5 seconds OFF
14-time fl ash
2.5 seconds OFF
6
16-time fl ash
2.5 seconds OFF
7
17-time fl ash
2.5 seconds OFF
8
'Outdoor unit
2-time fl ash
stops and
2.5 seconds OFF
9
restarts 3
minutes later'
is repeated.
3-time fl ash
2.5 seconds OFF
10
4-time fl ash
2.5 seconds OFF
11
5-time fl ash
2.5 seconds OFF
12
8-time fl ash
2.5 seconds OFF
13
10-time fl ash
2.5 seconds OFF
14
12-time fl ash
15
2.5 seconds OFF
13-time fl ash
2.5 seconds OFF
16
NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 10-6.1.
2. LED is lighted during normal operation.
The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the fl ashing frequency is "2".
ON
2.5-second OFF
OFF
OBH584A
Abnormal point/
Condition
Outdoor power sys-
Overcurrent protection cut-out operates 3 consecutive times
tem
within 1 minute after the compressor gets started.
Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor,
defrost thermistor, P.C. board temperature thermistor, outdoor
heat exchanger temperature thermistor or ambient tempera-
ture thermistor shorts or opens during compressor running.
Outdoor control sys-
Nonvolatile memory data cannot be read properly.
tem
(The left lamp of the OPERATION INDICATOR lamp on the
indoor unit lights up or fl ashes 7-time.)
Serial signal
The communication fails between the indoor and outdoor unit
for 3 minutes.
Stop valve/
Closed valve is detected by compressor current.
Closed valve
Outdoor unit
Outdoor unit is defective.
(Other abnormality)
4-way valve/
The 4-way valve does not work properly.
Pipe temperature
The indoor coil thermistor detects an abnormal temperature.
Outdoor refrigerant
A closed valve and air trapped in the refrigerant circuit are
system abnormality
detected based on the temperature sensed by the indoor and
outdoor thermistors and the current of the compressor.
Overcurrent protec-
Large current fl ows into the power module (IC700) (FH09/12)/
tion
IGBT module (IC700) (FH15).
Discharge tem-
Temperature of discharge temperature thermistor exceeds
perature overheat
241°F (116°C), compressor stops. Compressor can restart if
protection
discharge temperature thermistor reads 212°F (100°C) or less
3 minutes later.
Fin temperature
Temperature of the fi n temperature thermistor on the heat sink
/P.C. board tem-
exceeds 167 ~ 187°F (75 ~ 86°C) (FH09/12)/167 ~ 176°F
perature thermistor
(75 ~ 80°C) (FH15) or temperature of P.C. board temperature
overheat protection
thermistor on the inverter P.C.board exceeds 162 ~ 185°F (72
~ 85°C) (FH09/12)/158 ~ 167°F (70 ~ 75°C) (FH15).
High pressure pro-
Indoor coil thermistor exceeds 158°F (70°C) in HEAT mode.
tection
Defrost thermistor exceeds 158°F (70°C) in COOL mode.
Compressor syn-
The waveform of compressor current is distorted.
chronous abnormal-
ity
Outdoor fan motor
Outdoor fan has stopped 3 times in a row within 30 seconds
after outdoor fan start-up.
Each phase current
Each phase current of compressor cannot be detected nor-
of compressor
mally.
DC voltage
DC voltage of inverter cannot be detected normally.
0.5-second ON
2.5-second OFF
Condition
0.5-second ON
28
Remedy
• Reconnect connector of compres-
sor.
• Refer to 10-5.
"How to check
inverter/compressor".
• Check stop valve.
• Refer to 10-5.
"Check of outdoor
thermistors".
• Replace inverter P.C. board.
• Check connection between the in-
verter P.C. board and the relay P.C.
board. (FH15)
• Refer to 10-5.
"How to check
miswiring and serial signal error.
• Check stop valve.
• Refer to 10-2.2. "Flow chart of the
detailed outdoor unit failure mode
recall function".
• Refer to 10-5.
"Check of R.V.
coil".
• Replace the inverter P.C. board.
• Check for a gas leak in a
connecting piping etc.
• Check the stop valve.
• Refer to 10-5.
"Check of outdoor
refrigerant circuit".
• Reconnect connector of compressor.
• Refer to 10-5.
"How to check
inverter/compressor".
• Check stop valve.
• Check refrigerant circuit and refrig-
erant amount.
• Refer to 10-5.
"Check of LEV".
• Check around outdoor unit.
• Check outdoor unit air passage.
• Refer to 10-5.
"Check of outdoor
fan motor".
• Check refrigerant circuit and refrig-
erant amount.
• Check stop valve.
• Reconnect connector of compressor.
• Refer to 10-5.
"How to check
inverter/compressor".
• Refer to 10-5.
"Check of outdoor
fan motor.
• Refer to 10-5.
"Check of inverter
P.C. board.
• Refer to 10-5.
"How to check
inverter/compressor".
• It occurs with following case.
Instantaneous power voltage drop.
(Short time power failure) (FH15)
• Refer to 10-5.
"Check of power
supply". (FH15)
• Refer to 10-5.
"How to check in-
verter/compressor".
Inverter P.C. board
MUZ-FH09/12NA(H)
Flashing →
LED
MUZ-FH15NA(H)
Flashing
LED

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Muz-fh09nahMuz-fh12naMuz-fh12nahMuz-fh15nahMuz-fh15na

Table of Contents