Max. Refrigerant Piping Length; Max. Height Difference; Additional Refrigerant Charge - Mitsubishi Electric MUZ-FH09NA Service Manual

Mitsubishi electric split-type air conditioners outdoor unit service manual
Hide thumbs Also See for MUZ-FH09NA:
Table of Contents

Advertisement

MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
MUZ-FH09NA
MUZ-FH09NAH
MUZ-FH12NA
MUZ-FH12NAH
MUZ-FH15NA
MUZ-FH15NAH
ADDITIONAL REFRIGERANT CHARGE (R410A: oz.)
NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Outdoor unit
Model
precharged
MUZ-FH09NA
2 lb. 9 oz.
MUZ-FH09NAH
NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Outdoor unit
Model
precharged
MUZ-FH12NA
2 lb. 9 oz.
MUZ-FH12NAH
NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Outdoor unit
Model
precharged
MUZ-FH15NA
3 lb. 7 oz.
MUZ-FH15NAH
OBH584A
Refrigerant piping: ft.
Max. Length

Max. Height difference

A
65
100
Indoor
unit
Max. Height
difference
B
25
0
25
0
25
30
0
1.08
B
40
50
Max. Length
A
Outdoor unit
Refrigerant piping length (one way): ft.
30
40
1.08
3.24
Calculation: X oz. = 1.08/5 oz./ft. × (Refrigerant piping length (ft.) - 25)
Refrigerant piping length (one way): ft.
30
40
1.62
4.86
Calculation: X oz. = 1.62/5 oz./ft. × (Refrigerant piping length (ft.) - 25)
Refrigerant piping length (one way): ft.
40
50
60
3.24
5.40
7.56
Calculation: X oz. = 1.08/5 oz./ft. × (Refrigerant piping length (ft.) - 25)
12
Piping size O.D: in.
Gas
Liquid
3/8
1/2
50
60
5.40
7.56
50
60
8.10
11.34
70
80
90
9.72
11.88
14.04
1/4
1/4
65
8.64
65
12.96
100
16.20