MAX REFRIGERANT PIPING LENGTH

Piping length each indoor unit (a, b)
Total piping length (a+b)
Bending point for each unit
Total bending point
It is irrelevant which unit is higher.

ADDITIONAL REFRIGERANT CHARGE

Outdoor unit
Refrigerant piping length (one way, 2 unit total)
precharged
(g)
1,300
Calculation : Xg = 20 g/m x (Refrigerant piping length (m) - 20)
Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the
table below.
OBH626H
Sub muffler
Capillary tube
LEV A
Capillary tube
LEV B
30 m
20 m
0
200
Compressor
Discharge
temperature
thermistor RT62
Muffler
4-way valve
Indoor
a
units
20 m
30 m
20
30
b
For
Indoor unit A
Indoor unit B
72
Outdoor heat
exchanger
temperature
thermistor
RT68
FAN-OUT
Capillary tube
Strainer
#100
Distributor
Outdoor
unit
UNIT: mm (inch)
Outdoor unit union diameter
Liquid
Gas
Liquid
Gas
UNIT: mm
Ambient
temperature
thermistor
RT65
Defrost
thermistor
RT61
Max.
Height
difference
15 m
15 m
10 m
6.35(1/4)
9.52(3/8)
6.35(1/4)
9.52(3/8)