Service Port; To Outdoor Unit - Lennox Merit 13ACD-018 Installation Instructions Manual

Lennox merit series 13 acd units
Hide thumbs Also See for Merit 13ACD-018:
Table of Contents

Advertisement

SERVICE
PORT
SERVICE
PORT
OPEN
TO BOTH
INDOORAND
OUTDOOR
UNITS
SERVICE
PORT
(VALVE
STEM
SHOWN
OPEN)
INSERT
HEX WRENCH
HERE
TOINDOOR
UNIT
TO OUTDOOR
UNIT
STEM
CAP
Figure 4. Angle-Type Service Valve
(Back-Seated
Opened)
Operating
Bali-Type
Service
Valve
To Access Bali-Type Service Port:
A service port cap protects the service port core from
contamination and serves as the primary leak seal.
OPEN TO LINE SET WHEN VALVE IS CLOSED,
TO BOTH LINE SET AND UNIT WHEN VALVE IS
OPEN.
TO INDOOR UNIT
TO OPEN ROTATE STEM
COUNTERCLOCKWISE
90 ° .
BALL(SHOWN
CLOSED)
TO CLOSE
ROTATE STEM
CLOCKWISE
90 ° .
VALVE
STEM
CORE
SERVlCEPORTCAP
STEM CAP
Figure 5. Bali-Type Service Valve
1. Remove service port cap with an appropriately sized
wrench.
2. Connect gauge to the service port,
3. When testing is completed, replace service port cap and
tighten as follows:
With Torque Wrench:
Finger tighten and then
tighten per table table 1,
Without Torque Wrench: Finger tighten and use an
appropriately
sized wrench to turn an additional
1/6 turn clockwise as illustrated in figure 2,
To Open and Close Bali-Type Service Valve:
A valve
stem
cap
protects
the
valve
stem
from
contamination and assures a leak-free seal,
1. Remove stem cap with a wrench.
2. Use an appropriately sized wrench to open. To open
valve, rotate stem counterclockwise
90 ° . To close
rotate stem clockwise
90 ° ,
3. Replace the stem cap and tighten as follows:
With Torque Wrench:
Finger tighten and then
tighten per table 1,
Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional
1/12 turn clockwise as illustrated in figure 2,
NOTE - A label with specific torque requirements
may be
affixed to the stem cap. If the label is present, use the
specified torque,
Remove existing HCFC-22 refrigerant using one of the
following methods:
METHOD 1:
Use this method if the existing outdoor unit is not equipped
with manual shut-off valves, and plan on using existing
HCFC-22 refrigerant to flush the system.
NOTE - Use recovery machine instructions
for specific
setup requirements.
Perform the following task:
1. Disconnect all power to the existing outdoor unit,
2, Connect
to the existing
unit a gauge set, clean
recovery cylinder and a recovery machine. Use the
instructions provided with the recover machine on how
to setup the connections,
3. Remove all HCFC-22 refrigerant from the existing
system, Check gauges after shutdown to confirm that
the entire system is completely void of refrigerant,
RECOVERY
MACHINE
c p. COVERY
MANIFOLD
GAUGES
/
OUTDOOR
UNIT
Figure 6. Typical Refrigerant Recovery (Method 1)
505366M
01/08
Page 4