Individual Installation - LG ATNH126ELFC Service Manual

Indoor unit ceiling cassette-4way ceiling & floor(convertible) ceiling concealed duct outdoor
Hide thumbs Also See for ATNH126ELFC:
Table of Contents

Advertisement

Outdoor Unit_AUUH728C
1. Selection of the best location
• If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radia-
tion from the condenser is not restricted.
• Do not place animals and plants in the path of the warm air.
• Take the air conditioner weight into account and select a place where noise and vibration are minimum.
• Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
• Rooftop Installations : If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure
the roof structure and anchoring method are adequate for the unit location. Consult local codes regard-
ing rooftop mounting.

2. Individual installation

Basic Space required
• A space of at least 250 mm is nessary at the back for inlet air. Tacking servicing, a space of about 750 mm
should be provided at the front.
Rear
B
Front
A
service space
<Top View>
C
D
<Side View>
A : 750 mm or more
B : 250 mm or more
C : Top discharge(open in principle)
D : Front inlet(open in principle)
E
E : Rear inlet(open in principle)
Installation
Service Manual 45