LG ATNH126ELFC Service Manual page 41

Indoor unit ceiling cassette-4way ceiling & floor(convertible) ceiling concealed duct outdoor
Hide thumbs Also See for ATNH126ELFC:
Table of Contents

Advertisement

1. Decline Installation of indoor unit is very important for the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe should be 5mm.
• The unit must be or declined to wards drain hose while installation.
Drainage hole
CORRECT
CAUTION FOR GRADIENT OF
UNIT AND DRAIN PIPING
• Alway lay the drain with downward inclination
(1/50 to 1/100).
Prevent any upward flow or reverse flow in any
part.
• 5mm or thicker formed thermal insulator shall
always be provided for the drain pipe.
CORRECT
• Install the P-Trap (or U-Trap) to prevent
a water leakage caused by the blocking
of intake air filter.
Drain Pipe
Drain Pump
CAUTION
Front of view
Ceiling
INCORRECT
INCORRECT
1/50~1/100
1/50~1/100
MAX 700mm
Drainage hole
Lay the drain hose with a downware
inclination so water will drain out.
Unit
Make sure to be closed.
Applied U-Trap Dimension
A ≥ 70mm
B ≥ 2C
C ≥ 2 x SP
SP = External Pressure
(mmAq)
C
Ex) External Pressure
= 10mmAq
A ≥ 70mm
A
B ≥ 40mm
C ≥ 20mm
Installation
Thermal insulator
(Local supply)
Drainage pipe
(Local supply)
Drainage hole
B
U-Trap
Service Manual 41