Toshiba MCY-MHP0404HT-C Service Manual page 112

Multi type
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
Sub-code
controller
code
L07
L08
L08
L09
L10
L10
L20
Fan IPDU
A3-
1
2
IPDU
(Upper)
(Lower)
01
O
O
02
03
O
O
04
O
05
O
O
06
O
O
07
O
O
O
Circle (O): Faulty IPDU
(*) Concerning the "00" auxiliary
L
2
9
L
2
9
code
1) The wrong model setting
for the interface P.C. board
was used when the board
was replaced with the service
P.C. board.
In such a case, the sub-codes
"08" to "0F" for L29, which are
not included in the table above,
may be displayed.
2) The wrong model setting for
the fan IPDU P.C. board was
used when the board was
replaced with the service
P.C. board.
Detected
indoor address
L30
L30
L31
P01
P03
P03
Location
of
Description
System status
detection
Indoor
Connection of
Stop of
unit
group control
corresponding
cable to stand-
unit
alone indoor unit
Indoor
Indoor group /
Stop of
unit
addresses not
corresponding
set
unit
Indoor
Indoor capacity
Stop of
unit
not set
corresponding
unit
I/F
Outdoor
All stop
capacity not set
AI-NET
Duplicated
All stop
Indoor
central control
unit
address
I/F
Error in No. of
All stop
IPDUs
Indoor
External
Stop of
unit
interlock of
corresponding
indoor unit
unit
I/F
Extended IC
Continued
error
operation
Indoor
Indoor fan motor
Stop of
unit
error
corresponding
unit
I/F
Discharge
All stop
temperature TD
error
Error detection
condition(s)
There is at least one stand-
alone indoor unit to which
group control cable is
connected.
Address setting has not been
performed for indoor units.
Capacity setting has not been
performed for indoor unit.
Jumper wire provided on P.C.
board for servicing I/F P.C.
board has not been removed
as required for given model.
There is duplication in central
control address setting.
Insufficient number of IPDUs
are detected when power is
turned on.
• Signal is present at
external error input
terminal (CN80) for 1
minute.
There is part failure in P.C.
board (I/F).
Discharge temperature (TD)
exceeds 115 °C.
111
123
Check items (locations)
• Check indoor addresses.
• Check indoor addresses.
Note:
This code is displayed
when power is turned on
for the first time after
installation.
Set indoor capacity. (DN =
11)
Check model setting of P.C.
board for servicing outdoor
I/F P.C. board.
• Check central control
addresses.
• Check network adaptor
P.C. board.
• Check model setting of
P.C. board for servicing
outdoor I/F P.C. board.
• Check connection of UART
communication connector.
• Check A3-IPDU, fan IPDU,
and I/F P.C. board for
defect.
When external device is
connected to CN80
connector:
1) Check for defect in
external device.
2) Check for defect in indoor
P.C. board.
When external device is not
connected to CN80
connector:
1) Check for defect in indoor
P.C. board.
Check outdoor P.C. board
(I/F).
• Check the lock of fan motor
(AC fan).
• Check wiring.
• Check outdoor service
valves (gas side, liquid
side) to confirm full
opening.
• Check outdoor PMV for
clogging.
• Check resistance
characteristics of TD
sensor.
• Check for insufficiency in
refrigerant quantity.
• Check for defect in 4-way
valve.
• Check leakage of SV4
circuit.
• Check SV4 circuit (wiring
or installation error in SV4).
• Check leakage of SV5
circuit.

Hide quick links: